ABB Eagle Manual - Página 11

Procurar online ou descarregar pdf Manual para Equipamento industrial ABB Eagle. ABB Eagle 20 páginas. Self-powered single phase recloser for up to 27kv
Também para ABB Eagle: Manual de início rápido (4 páginas)

S O LU Z I O N I PA S S I V E , AT T I V E E P R E V E N T I V E

Technical Specifications

Technical Specifications for Hardware
Nominal Operating Voltage
Rated Max. Voltage
Rated Power Frequency
Rated Continuous Current
Rated Symmetrical Interrupting Current
Rated Short-Time Withstand Current
Rated Short-Time Withstand Duration
Rated Peak-Withstand Current
Rated BIL
Rated Power Frequency Wet Withstand (60s)
Creep Distance H1 to H2
Recloser Unit Weight
Auxiliary Power
Operating Temperature
Rated Number of Operations
Ingress Protection
Standards Compliance
Technical Specifications for Electronics & Software
Modes of Operation
Rated operating duty
Minimum Pickup Fault Current
Minimum current for Wi-Fi communication
Minimum Power-Up Time
Protection Functions
Other Functions
Current Sensor Accuracy
Operating Curves
Records
Communication
(1) Tripping/Reclosing capability is not dependent of availability of certain minimum pre-fault current.
Minimum current noted is for connecting to the unit wirelessly.
15/27 kV
27 kV
60 Hz
200 A
8 kA
8 kA
0.5 s
20.8 kA
125 kV
60 kV
668 mm
20 KG (44 Lbs)
12V DC (for programming)
-40C to +60C
10,000 Operations
IP65
IEEE C37.60/IEC 62271-111
Autorecloser
Sectionalizer
Breaker/Switch
Min O 0.2s CO 2s CO 2s CO Lockout
Max O 5s CO 5s CO 20s CO Lockout
10 A
5 A (
1
)
25 ms
3
50/51P (
)
2
nd
Harmonic Inrush Restraint
Cold Load Pickup
Non-Reclose/Hot Line Tag
Switch On To Fault
> 50A: ±1%
> 20A: ±2.5%
> 10A: ±5%
< 10A: ±1.6A
ANSI/IEC, Recloser, Fuse and Custom Curves
Events and Fault Records (1000)
Internal Device Events (100)
Disturbance Records (250)
Load Profile (60 days)
Security Log (1000)
Wi-Fi with WPA2 128 Bit-Encryption
Auto Disable Feature
Hide SSID Feature
11