Chromalox DTS-HAZ Manual de instruções de instalação - Página 9

Procurar online ou descarregar pdf Manual de instruções de instalação para Termostato Chromalox DTS-HAZ. Chromalox DTS-HAZ 12 páginas. Microprocessor based temperature control and power connection kit

Chromalox DTS-HAZ Manual de instruções de instalação
Programming
To program the digital Thermostat follow the instructions below:
Press
MODE
MODE
MODE
MODE
MODE
MODE
MODE

Troubleshooting

Alarm Type
Sensor Open
Sens err
Sensor Shorted
Sens err
Lo Temperature
Blinking between sensed
temperature and "LotP"
Hi Temperature
Blinking between sensed
temperature and "HitP"
EPR
EEprom memory error
ERR1
Program memory error
Parameter
Display
Set Point
High Temp
Low Temp
LotP
Dead Band
Temp. Units
UnIt
Soft Start
Alarm State
Display
Check if your sensor is correctly connected to the unit
Check if your sensor is correctly connected to the unit
Sensed temperature is below Lo Temp. Threshold. Alarm will be
cleared automatically when sens temp > lo threshold + 5 deg
Sensed temperature is above HI Temp. Threshold. Alarm will be
cleared automatically when sens temp < hi threshold - 5 deg
Press UP & DOWN keys for 2 seconds. Unit will be loaded with
default settings
Program memory corrupt. Solution: Reprogram the unit.
Consult Factory.
Action
Press UP or Down to adjust
StpT
the Set Point Temperature
Press UP or Down to adjust
HItp
the High Temperature Alarm
Press UP or Down to adjust
the Low Temperature Alarm
Press UP or Down to adjust
bAnd
the Dead Band From 2˚ to 100˚
Press UP or Down to toggle
between temp units: ˚F or ˚C
Press UP or Down to enable or
SSrt
disable the Soft Start Function
Press UP or Down to toggle
ALrM
Alarm State to be Normally Open
or Normally Closed
9
Solution
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN
UP
DOWN