9.
Error list
Status
The RZ-24 control can-
not be reset from the
alarm state.
Alarm condition does
not automatically reset
after the manual release
has been operated.
The LED on the housing
cover shows red when
the RZ-24 central unit
is in normal operating
mode and it shows
green when the RZ-24
central unit is in alarm
mode.
The LED on the housing
cover does not light up
or does not light up pro-
perly.
Possible causes
Remedy of the error
Terminals 8/9 not
If there is no external con-
bridged.
nection, then bridge termi-
nals 8/9.
Fire alarm loop has
Insert a 3.9 kΩ resistor in
no end resistance.
the last fire detector.
Open fire alarm loop Check that the fire detectors
are firmly seated in their
base.
Ribbon cable is torn/
Housing must be replaced.
defective.
There is a standard
Install optional reset board
reset board in the
for power failure and fire
housing.
(not included in standard
scope of delivery).
Defect of the housing
• Check the ribbon cable
cover of the RZ-24
control unit.
• Check the position of
Ribbon cable on the
reset board is not
• Check the position of
plugged in correctly.
Ribbon cable on the
• Disconnect the ribbon
reset board is not
plugged in correctly.
• Check the position of
Technical Manual
RZ-24 Central
for damage.
the ribbon cable on the
reset board.
the reset board on the
main board.
cable with the reset
board from the main
board and then recon-
nect it.
the ribbon cable on the
reset board.
Page 07.021.19