RZ-24-05 Central
2a) Demands
2b) Operational life
3)
Components of a
DICTATOR Hold-Open
System with
RZ-24-05
Page 07.021.04
Page 07.021.4
2. General Regulations for Hold-Open System
In Germany, the installation of a hold-open system is regulated by the
general building inspection approval or type approval of the DIBt. For
European countries without national regulations, EN 14637 is used as
a guideline.
These regulations also govern:
-
the mounting positions and number of fire detectors
-
the position and design of the hand switch
-
the acceptance test (first placing in service) and marking
-
the recurring functional tests and maintenance
-
the requirements for the qualification of the persons testing
and maintaining
The documents are available under www.dictator.de. The general type
approval DIBt also includes all permissible device combinations.
For further instructions on installation, use, maintenance, functional
testing and servicing as well as documentation, please refer to our
operating manual for hold-open systems, which is available to our
authorised specialists for DICTATOR hold-open systems.
The device combinations "RZ-24" and "RZ-24-05" should be
mounted in the detection range of one of the fire detectors of the
respective door. If not, an additional detector is required.
To ensure the correct functioning of the hold-open system, the DICTA-
TOR smoke and heat detectors have to be replaced after a maximum
of 8 years of operational life. In Germany the DIN 14677 regulates the
replacement obligation of fire detectors in hold-open systems.
The DICTATOR hold-open system may comprise a maximum of 20 smoke
and/or heat detectors. (ATTENTION: observe the maximum output load
of the RZ-24-05 central!).
Components:
- RZ-24-05 central with power pack, part no. 040563
- RM 4000 smoke detector or WM 4000 heat detector with base, part
no. 040860SET or 040861SET
- Resistor 3.9 kΩ (included in the delivery of the RZ-24-05)
- Magnet (DICTATOR electromagnets EM GD 50 to EM GD 70 - see
separate catalogue pages)
- Push button of the RZ-24-05 central, further push button switches can
be connected in the detector loop, e.g. part no. 040005
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20200513