Epever LS-B Series Manual - Página 2
Procurar online ou descarregar pdf Manual para Inversor Epever LS-B Series. Epever LS-B Series 2 páginas. Solar charge controller
HUIZHOU EPEVER TECHNOLOGY CO., LTD.
C. Low Voltage Reconnect Voltage > Low Voltage Disconnect Voltage ≥ Discharging
Limit Voltage.
D. Under Voltage Warning Reconnect Voltage > Under Voltage Warning Voltage ≥
Discharging Limit Voltage.
E. Boost Reconnect Charging voltage > Low Voltage Disconnect Voltage.
CAUTION: Please refer to the user manual or contact the sales for the
details of the setting operation.
(2) Load Mode
1) Manual Control(default ON)
The load is turned ON/OFF via the button or remote command.
2) Light ON/OFF
3) Light ON/OFF + Timer
4)Time Control
Control the load on/off time by setting a real-time clock.
6 Protections
PV over current
When the charging power of the PV array exceeds its rated charging power, it will be
charged at the rated charging power.
PV short circuit
The controller will stop charging when the input terminal of the PV array is short-
circuited. After clearing the faults, the charging will resume automatically.
PV reverse polarity
When the polarity of the PV array is reversed, the controller may not be damaged and
can continue to operate normally after the polarity is corrected.
Battery reverse polarity
When the polarity of the battery is reversed, the controller may not be damaged and
can continue to operate normally after the polarity is corrected.
Battery over voltage
When the battery voltage reaches the overvoltage disconnect voltage, the controller will
automatically stop charging the battery to prevent battery damage caused by over-
charging.
Battery over-discharge
When the battery voltage reaches the low voltage disconnect voltage, the controller will
automatically stop discharging the battery to prevent battery damage caused by over-
discharging. (Any controller-connected loads will be disconnected. Loads directly
connected to the battery will not be affected and may continue to discharge the
battery.)
Battery over temperature
The controller detects the battery temperature through an external temperature sensor.
The battery will stop working when its temperature exceeds 65 °C and resume at below
55 °C.
Overload
The controller automatically cuts off the output when the load current exceeds 1.05
times the rated discharge current. After the load reconnects automatically five times
(delay of 5s, 10s, 15s, 20s, 25s), please reduce the electrical equipment. And then,
press the load ON/OFF button, restart the controller, or wait for one night-day cycle
(night time > 3 hours) to eliminate the overload fault.
Load short circuit
When the load is short-circuited (The short circuit current is higher than or equal to 2
times the rated discharge current), the controller automatically cuts off the output. After
the load reconnects automatically five times (delay of 5s, 10s, 15s, 20s, 25s), please
press the load ON/OFF button, restart the controller, or wait for one night-day cycle
(night time > 3 hours). Then the load reconnection automatically will resume.
Controller over temperature
An internal temperature sensor can detect the internal temperature of the controller.
The controller stops working when its internal temperature exceeds 85 °C and resumes
when it is below 75 °C.
Turn-On voltage (Adjustable):
5V(12Vsystem), delay10min.
Turn-Off voltage (Adjustable):
6V(12Vsystem), delay10min.
Note: 24V system voltage×2
3
Tel: +86-752-3889706
TVS high voltage transients
The internal circuitry of the controller is designed with Transient Voltage Suppressors
(TVS), which can only protect against the high-voltage surge pulses with less energy.
Suppose the controller is to be used in an area with frequent lightning strikes. In that
case, it is recommended to install an external surge arrester.
7 Troubleshooting
Faults
Possible reasons
The charging indicator does
not light up when there is
PV array
sufficient direct sunlight on
disconnection
the PV array.
The wire connection is
Battery voltage is
correct, but the controller is
lower than 8V
not working.
The battery green indicator
Battery over
fast flashing
voltage
The red battery indicator on
Battery over-
solid
discharged
The red battery indicator
Battery over
slowly flashing
temperature
Charge, Load, and
Controller over
Battery(orange)indicator
temperature
flashing
Load red indicator slowly
Overload
flashing
Load red indicator fast
Load short circuit
flashing
8 Technical Specifications
Item
LS1024B
System nominal voltage
Battery type
Rated charge current
10A
Rated discharge current
10A
Working voltage range of
controller
Max. PV open circuit
voltage
Self-consumption
Charge circuit voltage
drop
Discharge circuit voltage
drop
Temperature
compensate coefficient
Environment temperature
Relative humidity
Enclosure
Grounding
Dimension(mm)
138.6x69.3x37
Mounting size
126mm
Φ4.3
Mounting hole size
Terminal
4mm
Net weight
0.13kg
9 Disclaimer
This warranty does not apply under the following conditions:
Damage from improper use or use in an unsuitable environment.
PV or load current, voltage, or power exceeds the rated value of the controller.
The controller's working temperature exceeds the limit working environment
temperature.
User disassembly or attempted to repair the controller without permission.
The controller is damaged due to natural elements such as lighting.
The controller is damaged during transportation and shipment.
Any changes without prior notice! Version number:V3.3
Website: www.epever.com
Troubleshooting
Confirm that PV and battery wire
connections are correct and tight
Please check the voltage of the
battery. At least 8V voltage to
activate the controller.
Check
whether
the
voltage is higher than OVD (over
voltage disconnect voltage), and
disconnect the PV.
Waiting for the battery voltage to
be restored to or above LVR (low
voltage reconnect voltage) or
changing the power supply in
other ways.
The controller will resume when
the battery temperature declines
to below 55 ºC.
When the heat sink of the
controller exceeds 85 ℃ , the
controller will automatically cut off
the input and output circuit. When
the temperature bellows to 75℃,
the controller will resume work.
① Please reduce the number of
electric equipment.
② Restart the controller or press
the load ON/OFF button.
③ Wait for one night-day cycle
(night time>3 hours).
① Check carefully loads
connection, clear the fault.
② Restart the controller or press
the load ON/OFF button.
③ Wait for one night-day cycle
(night time>3 hours).
LS2024B
LS3024B
12/24VDC Auto
Sealed/Gel/Flooded/User
20A
20A
8~32V
50V
≤8.4mA/12V;≤7.8mA/24V
≤0.28V
≤0.20V
-3mV/℃/2V (default)
-35℃~+50℃
≤95% (N.C.)
IP30
Common positive
159.6x81.4x47.8
200.6x101.3x57
147x50mm
190x70mm
Φ4.3
Φ4.5
2
2
10mm
10mm
0.3kg
0.5kg
4
battery
30A
30A
2