ABB ACS 400 Manual de instalação - Página 3
Procurar online ou descarregar pdf Manual de instalação para Controlador ABB ACS 400. ABB ACS 400 4 páginas.
Replace the front cover:
1. First hook the bottom end fingers.
2. Click the retaining lever to its place.
3. Replace the control panel if available.
STOP!
CHECK that starting the motor does not cause any danger. If there is a risk of
damage to the driven equipment in case of incorrect rotation direction of the motor, it
is recommended having the driven equipment disengaged when first start is
performed.
NO CONTROL PANEL:
Note! The drive may start when mains
is switched on.
For analogue speed reference,
connect potentiometer (2-10 kΩ) to
terminals 1-4.
Default setting for AI1 is voltage.
As default motor nominal values are
400(230) V and 50 Hz and 1440 rpm.
To start the drive activate digital input
DI 1.
As default digital input DI 2 is
deactivated and the rotation direction
is forward. To reverse the rotation
direction activate DI 2.
Switch on mains.
Note! For further information on I/O settings, refer to User's Manual for product type ACS 400.
CONTROL PANEL:
Proceed with the step 11.
8
9
10
I/O TERMINAL (X1) WIRING
CABLE EARTHING
SPEED SETTING
POTENTIOMETER
DIRECTION
6&5
$,
$*1'
9
$,
$*1'
$2
$*1'
9
/
START
STOP
'&20
',
',
',
',
',
'&20