Accurex Vari-Flow Manual de instalação, operação e manutenção - Página 10

Procurar online ou descarregar pdf Manual de instalação, operação e manutenção para Ventilador Accurex Vari-Flow. Accurex Vari-Flow 16 páginas. Air management system

Temperature Sensors -
Temp Sensor on EF4*
T1 to EF4
T2 to EF4
T3 to EF4
T4 to EF4
T5 to EF4
T6 to EF4
T7 to EF4
T8 to EF4
Temperature Sensor on EF5*
T1 to EF5
T2 to EF5
T3 to EF5
T4 to EF5
T5 to EF5
T6 to EF5
T7 to EF5
T8 to EF5
Temperature Sensors Connected
T1
T2
T3
T4
Temperature Interlock (IMC Compliance)
Temp Interlock*
TempInt Enabled
Set Point
Off Delay Time
Make-Up Air
Make-Up Air Set Points*
MUA Mode
Pressure
Set Point
MUA Speed
Max Speed Set*
* To see values, you need to log in.
10
Vari-Flow Air Management System
continued
Descriptors/Value Default
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
No
No / Yes
Yes
No / Yes
No
No / Yes
No
No / Yes
No
No/Yes
Yes
°F
90°F
Minutes
10 min
Pres / Trak
Pres
Inches of WC x 100
-
Inches of WC x 100
5
0-100%
-
0-100%
100%
Use
Indicates if T1 is linked to EF4
Indicates if T2 is linked to EF4
Indicates if T3 is linked to EF4
Indicates if T4 is linked to EF4
Indicates if T5 is linked to EF4
Indicates if T6 is linked to EF4
Indicates if T7 is linked to EF4
Indicates if T8 is linked to EF4
Indicates if T1 is linked to EF5
Indicates if T2 is linked to EF5
Indicates if T3 is linked to EF5
Indicates if T4 is linked to EF5
Indicates if T5 is linked to EF5
Indicates if T6 is linked to EF5
Indicates if T7 is linked to EF5
Indicates if T8 is linked to EF5
Indicates if T1 is connected
Indicates if T2 is connected
Indicates if T3 is connected
Indicates if T4 is connected
If set to yes, Temperature Interlock feature
is enabled. Exhaust fan will start if hood
temperature exceeds the Temperature Interlock
set point and will run until the hood temperature
falls below set point for the off delay time.
If the temperature of the hood exceeds this set
point, the exhaust fan will start automatically
regardless of the operating mode of the fan
selected by the operator.
The amount of time the fans remain on after
the temperature in the hood goes below the
temperature set point.
Indicates the operating mode of the MUA
Differential air pressure measured from the
control space to the outside or adjacent room.
The desired space pressure set point.
(adjustable from -.30" WC to + .30" WC)
The actual output speed for the MUA
The maximum output control limit for the MUA
VFD or damper set. Must be set to a value
that ensures proper design full flow CFM.
(Adjustable from 0% to 100%)