U N I V E R S A L M O T O R C O N T R O L L E R U M C 1 0 0 . 3
PROFIBUS Line in Drawout Systems where PDP32.0 is installed in Cable Chamber
The following figure shows a simplified diagram on how to connect the UMC100.3 to a PROFIBUS network if the UMC100.3 is
inside a drawer and the PROFIBUS communication interface is mounted outside the drawer e.g. in the cable compartment. In
drawout systems this solution has several benefits:
• PROFIBUS address is stored in the PROFIBUS communication interface in addition to the UMC100.3.
In case of a drawer replacement the new — not addressed — UMC100.3 takes over the bus address automatically.
Fast reparameterisation without manual interaction possible.
• Swapping of drawers detected if "Address Check" in UMC100.3 enabled. In other words, it is not possible to accidentally
start the wrong motor because of a swapped drawer.
The required grounding of the PROFIBUS cable is not shown in this figure.
PROFIBUS
Master
L
T
Repeater
L
T
Repeater
Optional connection of configu-
ration adapter
(2a)
(2b)
(1)
5
5
(4)
max. 3m
Service laptop
Configuration adapter
UTP22
(1)
24V DC supply for the commu-
(3)
nication interface. This lets
the PDP32 stay active even in
case the drawer is withdrawn.
(2a) Ready made connection cable
from SMK3.0 X1 to the backside
of the drawer
(2b) Ready made connection cable
from inside drawer to UMC100.3
(3)
UMC100.3 mounted inside a
drawer
(4)
PROFIBUS communication inter
face with mounting kit
Termination active