the Class 2 conductors are to be installed in the
wallbox with the power conductors. Use
approved connectors (supplied by others) to
make Class 2 connections inside the wallbox.
•
CAUTION
: TO REDUCE THE RISK OF
OVERHEATING AND POSSIBLE DAMAGE
TO OTHER EQUIPMENT, DO NOT INSTALL
TO CONTROL A RECEPTACLE.
•
Wiring: Use copper wire only. For supply
connection, use wires rated for at least 75°C.
•
Load Type: The -SW, -SWS, and -SLVS are
designed for use with permanently installed
incandescent, fluorescent (non-dimmable), low
voltage, neon/cold cathode, HID, general
purpose fan, or tungsten halogen lighting.
•
Temperature: The -SW, -SWS, and -SLVS are
designed to be used where temperatures are
between 32° to 104°F (0° to 40°C).
•
Wallboxes: Devices mount in standard
wallboxes. For easy installation, Crestron
recommends using 3 ½" deep wallboxes. Several
devices can be installed in one wall box
(multigang). This requires the removal of side
sections (refer to diagram on page 3) and the
derating of the switching device. For a smooth
appearance, one-piece multigang faceplates (not
supplied) can be installed.
•
Other Switch Devices: Mechanical 3- or 4-way
switches will not work with the -SW, -SWS, or
-SLVS.
•
Spacing: If mounting one device above another,
leave at least 4 ½" vertical space between them.
Multigang Installations
In multigang installations, several controls are grouped
horizontally in one wallbox. For a smooth appearance,
one-piece multigang faceplates (not supplied) can be
installed.
1. When combining controls in a wallbox, remove
inner side sections prior to wiring (refer to the
following figure).
Installation Guide – DOC. 6134B
CLW-SW, SWS, & SLVS(W/A/B)
Inner Sections of Multiganged Switches
DO NOT REMOVE OUTER SECTIONS
The load capacity must also be derated. The following
charts provide derating information for various
applications.
Derating Information for Incandescent, Tungsten Halogen,
and Electronic Low Voltage Applications
Part Number
Removed
-SW
-SWS
-SLVS
Derating Information for Magnetic Low Voltage and
Neon/Cold Cathode Applications
Part
No Side
Number
Removed
-SW
1000VA/750W
-SWS
1000VA/750W
-SLVS
*
VA ratings are for input power to the transformer. If you do not
know the input power requirement of the transformer, use the bulb's
wattage rating to determine proper rating.
Derating Information for Fluorescent/HID Applications
Part
Number
Removed
-SW
-SWS
-SLVS
Derating Information for General Purpose Fans
Part
Number
Removed
-SW
-SWS
-SLVS
2. To remove a side section, bend the side section
back and forth with a pair of pliers until the
Stand Alone Wall Box Switch: CLW-SW, SWS, & SLVS • 3
REMOVE INNER SECTIONS
No Side
One Side
Removed
1000W
600W
1000W
600W
No Derating Necessary
*
One Side
Removed
600VA/450W
600VA/450W
No Derating Necessary
No Side
One Side
Removed
8A
5A
8A
5A
No Derating Necessary
No Side
One Side
Removed
3A
3A
3A
3A
No Derating Necessary
Two Sides
Removed
400W
400W
Two Sides
Removed
400VA/300W
400VA/300W
Two Sides
Removed
3A
3A
Two Sides
Removed
3A
3A