Siemens 3TS1722-0A 5-8K Series Instruções de utilização - Página 2
Procurar online ou descarregar pdf Instruções de utilização para Equipamento industrial Siemens 3TS1722-0A 5-8K Series. Siemens 3TS1722-0A 5-8K Series 2 páginas. Contactor for capacitor switching
Permissible Conductor Size: Main Terminals
Termination Data - Contactor
Finely Stranded with ring type cable lug
Terminal bar (max. width)
Screw Size
Tightening Torque
B. Installation
1. Permitted mounting positions are indicated in Fig.2
2. The unit is suitable for screw mounting on flat vertical
surface with two M4 screws. Always use plain and spring
washers.
Note: Install the unit in housing if it is exposed to dust, dirt,
contamination or aggressive atmosphere.
Fig. 2
E. Overall Dimensions
Dimensions in mm : 50 kVAr (3TS1722-0A .. 5-8K)
Fig. 3
Siemens product are environment friendly, which predominantly
consist of recyclable materials.
For disposals we recommend disassembling and separation into
following materials:
METALS: Segregate into Ferrous & Non Ferrous types for recycling
through authorised dealer.
Customer Care Toll free no. 1800 209 0987
Siemens Ltd.
I-IA-CECP-793
(This replaces SGR-03IO-1113)
C. Maintenance
• Remove dust by suction.
3TS1722-0A .. 5-8K
• Replacement of coil available as spare.
1 x 35mm² / 2 x 16mm²
12mm
M6
4-6 N-m
• Spare contact kits available.
• Contact Siemens Sales office for details.
• Handle the resistor wires carefully.
D. Note:
Normally the power factor controller in APFC panels, has the
provision for adjustment under voltage cut out with respect
to voltage and time. Please ensure that the controllers are
present as per values given in the table below
In case, Power factor controller does not have the provision
of above settings, it is recommended to provide a separate
undervoltage monitor having settings as per table, to ensure
satisfactory performance of the contactors.
For further details on such an undervoltage monitor, please
contact nearest Siemens office
Disposal
PLASTICS: Segregate as per material type for recycling through
authorised dealer. Because of the long lifetime of Siemens
products the disposal guidelines may be replaced by other national
regulations when taking the product out of service.
The local customer care service is available at any time to answer
disposal-related questions
Email: [email protected]
Product development is a continuous process. Consequently
the data indicated in this Leaflet is subject to change without
prior notice. For latest issue contact our sales offices.
Order Code
3TY7 463-0AF0
3TY7 463-0AP0
3TY7 463-0AR0
Coil Voltage
Under Voltage
110V
≥ 94 V
230V
≥ 196 V
415V
≥ 353V
Order No. A5E33259242000A Rev AB
AC Coil Voltage
110
230
415
Controller settings
Actuating time
< 0.1 sec
< 0.1 sec
< 0.1 sec
SACHIN ENTERPRISE