Siemens SIMATIC ET 200AL Manual - Página 12

Procurar online ou descarregar pdf Manual para Equipamento industrial Siemens SIMATIC ET 200AL. Siemens SIMATIC ET 200AL 38 páginas. 10-link digital output module dq 8x24vdc/2a 8xm12
Também para Siemens SIMATIC ET 200AL: Manual (38 páginas), Manual (50 páginas), Manual (32 páginas), Manual (37 páginas), Manual do equipamento (46 páginas), Manual (26 páginas), Manual do equipamento (28 páginas), Manual do equipamento (27 páginas), Manual (25 páginas)

Siemens SIMATIC ET 200AL Manual
Product overview
2.3 Functions
Requirements
The following table shows the software requirements for the use of PROFINET IO functions
with the IM 157-1 PN interface module.
Table 2- 1
Real-time communication
Isochronous real-time commu-
nication
Device replacement without
programming device
Media redundancy
Shared device
Use a S7-1500 CPU as a controller to use a shared device with STEP 7 (TIA Portal).
1
Systems of third-party manufacturers: Depending on the range of functions of the third-party sys-
2
tem
Real-time communication
A transmission method for PROFINET IO based on a cyclic data exchange with a provider-
consumer model.
Isochronous real-time communication
Synchronized transmission method for cyclic exchange of IRT data between PROFINET
devices. A reserved bandwidth within the send clock is available for IRT data. The reserved
bandwidth ensures that IRT data can be transferred at reserved synchronized intervals,
without being influenced by other higher network loads (e.g., TCP/IP communication, or
additional real-time communication).
A topological configuration is required for IRT.
Note
IO controller as sync master with IRT communication
We recommend that you also operate the IO controller as a sync master when configuring
IRT communication.
Otherwise IRT and RT configured IO devices may fail if the sync master fails.
12
Software requirements for PROFINET IO functions
PROFINET IO function
Configuration software
STEP 7 (TIA Portal) V13 or
higher
(with GSD file)
X
X
X
X
X
1
Interface module IM 157-1 PN (6ES7157-1AB00-0AB0)
STEP 7 V5.5 SP4 or higher
(with GSD file)/Software from
third-party manufacturer
X
X
X
X
X
Manual, 12/2016, A5E32347036-AD
2