Também para Siemens simatic ET 200MP: Manual (40 páginas), Manual (24 páginas), Manual (29 páginas), Manual (26 páginas), Manual (28 páginas), Manual (50 páginas), Manual (34 páginas), Manual do utilizador (44 páginas), Manual (30 páginas), Manual (25 páginas), Manual (42 páginas), Manual (28 páginas), Manual (33 páginas), Manual (49 páginas), Manual (36 páginas), Manual (39 páginas), Manual (28 páginas), Manual do equipamento (35 páginas), Manual do equipamento (32 páginas), Manual (29 páginas), Manual (34 páginas), Manual (36 páginas), Manual do equipamento (50 páginas), Manual (45 páginas)

Siemens simatic ET 200MP Manual
PROFINET interface X1 with 2-port switch (X1 P1 R and X1 P2 R)
The pin assignment of the ports depends on the setting of the port option "Activate
autonegotiation".
● Port P1 X1 R: When autonegotiation is deactivated, the RJ45 socket is allocated as data
terminal equipment MDI (normal pin assignment).
● Port P2 X1 R: When autonegotiation is deactivated, the RJ45 socket is allocated as a
switch MDI-X (crossed pin assignment).
● The following applies to both ports: When autonegotiation is activated, autocrossing is in
effect and the RJ45 socket is allocated either as data terminal equipment MDI or a switch
MDI-X.
The figure below shows the location of the PROFINET interface X1 and the connection
socket for the 24 V DC supply voltage.
Figure 3-1
Note
You need a screwdriver (max. blade width 2.5 mm) to remove the PROFINET plug.
Note
IM 155-5 PN ST interface module (6ES7155-5AA00-0AB0)
For the IM 155-5 PN ST with order number 6ES7155-5AA00-0AB0, note that the ports of the
PROFINET interface X1 are offset by 90°.
Interface module IM 155-5 PN ST (6ES7155-5AA01-0AB0)
Manual, 11/2017, A5E03612323-AC
Port P1 X1 R (front)
Port P2 X1 R (rear)
Connection socket 24 V DC supply voltage
Location of the PROFINET ports and the 24 V DC connection socket (view from below)
Wiring
3.1 Terminal assignment