Siemens SIMATIC ET 200SP HA Manual do equipamento - Página 30

Procurar online ou descarregar pdf Manual do equipamento para Equipamento industrial Siemens SIMATIC ET 200SP HA. Siemens SIMATIC ET 200SP HA 38 páginas. Distributed i/o devices busadapter for distributed i/o
Também para Siemens SIMATIC ET 200SP HA: Manual (32 páginas), Manual (50 páginas), Manual (34 páginas), Manual (38 páginas), Manual do equipamento (44 páginas), Manual do equipamento (50 páginas), Manual do equipamento (38 páginas), Manual do equipamento (46 páginas), Manual do equipamento (42 páginas), Manual do equipamento (44 páginas), Manual do equipamento (36 páginas)

Siemens SIMATIC ET 200SP HA Manual do equipamento
Technical specifications
Article number
General information
Firmware version
Usable terminal block
Color code for module-specific color identifica‐
tion plate
Engineering with
Redundancy
Supply voltage
Rated value (DC)
permissible range, lower limit (DC)
permissible range, upper limit (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
Current consumption, max.
Power loss
Power loss, typ.
Address area
Address space per module
Switching frequency
Relay outputs
Switching capacity of contacts
Cable length
30
FW update possible
SPPA-T3000 can be configured/integrated
from version
Redundancy capability
Address space per module, max.
with inductive load, max.
on lamp load, max.
Number of relay outputs
external protection for relay outputs
– with inductive load, max.
– with resistive load, max.
– Switching current, min.
– Rated switching voltage (DC)
– Rated switching voltage (AC)
shielded, max.
unshielded, max.
6DL1132-6HD50-0EK0
V1.0
Yes
TB type K0
CC40
V8.0
No
24 V
19.2 V
28.8 V
Yes
50 mA; At 24 V and energized changeover coils
60 mA; At 19.2 V and energized changeover coils
2.8 W; At 24 V, energized changeover coils and 5 A
current across each changeover contact
6 byte; PII: 0 bytes, +1 byte for QI information, +2
bytes of PROFINET status data; PIO: 1 byte, +2 bytes
of PROFINET status data
0.5 Hz
2 Hz
4
yes; 6 A, see data in manual
2 A; 2 A (24 V DC), 0.5 A (60 V DC), 0.1 A (120 V DC)
5 A; 5 A (30 V DC), 5 A (230 V AC)
8 mA
24 V; 24 V DC to 120 V DC
230 V; 24V AC to 230V AC
1 000 m
200 m
RQ 4x120VDC-230VAC/5A CO HA
Equipment Manual, 07/2022, A5E39389042-AF