Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manual - Página 35
Procurar online ou descarregar pdf Manual para Equipamento industrial Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA. Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA 38 páginas. Digital output module
Também para Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA: Manual do equipamento (36 páginas)
![Siemens SIMATIC ET 200SP HA DQ 32x24VDC/0.5A HA Manual](/uploads/products/server2/5207151/5207151.jpg)
Diagnostics
Error code
message
Channel/compo‐
1F
H
nent temporarily
unavailable
Module is faulty
100
H
Short-circuit to M 106
H
Shutdown on
122
H
button activation
Retentive memo‐
154
H
ry in carrier mod‐
ule defective
Retentive memo‐
155
H
ry in the terminal
block defective
Maintenance events
A maintenance event is generated for each maintenance required identified. The MT LED
lights up on the module.
Maintenance messages have no direct effect on the function of the module or digital outputs.
Table A-2
Maintenance messages, their meaning and possible remedies
Maintenance
Error code
message
Retentive mem‐
154
H
ory in carrier
module defective
Retentive mem‐
155
H
ory in the termi‐
nal block defec‐
tive
A.2.4
Address space
Abbreviations
● "IB" stands for input byte, that is, the module start address in the input area
● "QB" stands for output byte, that is the module start address in the output area
● "DQn" stands for digital output n
● "QDQn" stands for the value status (QI) of digital output n
Digital output module DQ 32x24VDC/0.5A HA (6DL1132-6BL00-0PH1)
Manual, 09/2018, A5E39265993-AA
Drivers, parameters, diagnostics messages and address space
A.2 Parameters, diagnostics messages and address space without PCS 7
Assign‐
Meaning
ment
Module
Firmware update is in progress or has been
canceled during the update. The module gen‐
erates no process and substitute values in
this state.
Module
Module is faulty
Channel
Short-circuit of the actuator supply to ground
Only effective in the connected state: Output
value=1
Module
The output disable switch was activated.
Module
Fault detected in the memory block on the
carrier module during startup.
Module
Fault detected in the memory block on the
terminal block during startup.
Assign‐
Meaning / Cause
ment
Module
Fault detected in the memory block on the
carrier module during operation.
Module
Fault detected in the memory block on the
terminal block during operation.
Remedy
● Restart the firmware update
● Wait for firmware update
Replace I/O module
Correction of the process wiring
Pull module
Replace carrier module
Replace terminal block
Remedy
Replace carrier module
Replace terminal block
35