Siemens SIMATIC NET Manual de instalação - Página 45

Procurar online ou descarregar pdf Manual de instalação para Equipamento industrial Siemens SIMATIC NET. Siemens SIMATIC NET 48 páginas. Network components bus terminal
Também para Siemens SIMATIC NET: Manual de Instruções (29 páginas), Manual de Instruções (50 páginas), Manual de Instruções (28 páginas), Manual de instruções de montagem (6 páginas), Informações sobre o produto (6 páginas), Manual de instalação (40 páginas), Manual de instalação (50 páginas), Manual de instalação (40 páginas), Manual de referência (14 páginas), Manual de instalação (34 páginas), Manual de Instruções (32 páginas)

Siemens SIMATIC NET Manual de instalação
Certification
6.2 EMC and Environmental Type Tests
6.2

EMC and Environmental Type Tests

The RUGGEDCOM M2100F has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Tests per IEC 61850-3
Note
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
36
In the case of an all fiber port configuration, this product meets all Class 2
requirements. Otherwise, all Class 1 requirements are met for copper ports.
If the unit contains copper ports, the IEC 1613 conformance is Class 1, during
which disturbance errors may occur but recovery is automatic.
If the unit contains all fiber ports, the IEC 1613 conformance is Class 2, during
which no disturbance errors will occur.
Test
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Induced
(Conducted) RFI
Magnetic Field
Voltage Dips
and Interrupts
Description
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
AC Power Ports
Test Levels
Severity Levels
±8 kV
±15 kV
20 V/m
±4 kV @ 2.5 kHz
±4 kV
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
±2 kV Line-to-
Ground, ±1 kV
Line-to-Line
±4 kV Line-to-
Ground, ±2 kV
Line-to-Line
10 V
100 A/m
Continuous
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
100% for 5 periods
100% for
50 periods
RUGGEDCOM M2100F
Installation Manual, 04/2022, C79000-G8976-1342-09
4
a
Note
a
Note
4
4
3
4
3
5