Certification
6.1.9 RoHS
A copy of the Declaration of Conformity is available via Siemens Industry Online
Support at https://support.industry.siemens.com/cs/ww/en/view/89855782.
6.1.9

RoHS

This device is declared by Siemens Canada Ltd. to meet the requirements of the
following RoHS (Restriction of Hazardous Substances) directives for the restricted use
of certain hazardous substances in electrical and electronic equipment:
A copy of the Material Declaration is available online at
support.industry.siemens.com/cs/ww/en/view/109738831.
6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS1600 has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
30
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic
Information Products
Test
Description
ESD
Radiated RFI
Burst (Fast
Transient)
Surge
Enclosure
Contact
Enclosure Air
Enclosure Ports
Signal Ports
± 4 kV @ 2.5 kHz
DC Power Ports
AC Power Ports
Earth
Ground Ports
Signal Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth,
± 2 kV Line-to-Line
https://
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV
± 4 kV
± 4 kV
Installation Manual, 11/2022, C79000-G8976-1013-04
Severity
Levels
4
4
x
x
4
4
4
4
3
4