Parameter
Parameter text
Note: To change P0595 you first need to set P0010 = 5, and then set P0010 back to 0 afterwards.
p595
Selecting technological units
p596
Reference quantity, technological units
p753[0]
CU analog inputs smoothing time constant, AI0 (T. 3/4)
p756[0]
CU analog inputs type, AI0 (T. 3/4)
p1015[0]
CO: Fixed speed setpoint 15
p1080[0]
Minimum speed
p1113[0]
BI: Setpoint inversion
p1210
Automatic restart, mode
Note: When using ECO mode, set P1335 = 100% to enable slip compensation for correct operation.
p1300[0]
Open-loop/closed-loop control operating mode
p1335[0]
Slip compensation, scaling
p2200[0]
BI: Technology controller enable
Note: Set pressure setpoint to suit application. This example assumes a 0-500Pa range sensor is used (e.g. QBM66.202 hi-range).
p2201[0]
CO: Technology controller, fixed value 1
p2253[0]
CI: Technology controller setpoint 1
p2264[0]
CI: Technology controller actual value
p2267
Technology controller upper limit actual value
p2268
Technology controller lower limit actual value
p2280
Technology controller proportional gain
p2285
Technology controller integral time
p2292
CO: Technology controller minimum limiting
p2302
Technology controller output signal starting value
p3880
BI: ESM activation
p3881
ESM setp source
Note: The following read-only parameters are shown as handy points of interest. Do not try to program these into your drive.
r755[0]
CU analog inputs actual value in percent, AI0 (T. 3/4)
r2260
CO: Technology controller setpoint after ramp-function generator
r2272
CO: Technology controller actual value scaled
r2294
CO: Technology controller output signal
Page 43 of 50
Building Technologies
Parameter Value
[5] Pa
500
500
[0] Unipolar voltage input (0 V ... +10 V)
1350
300
0
[26] Acknowledging all faults and reclosing for
an ON command
[7] U/f control for a parabolic characteristic and
ECO
100
Control_Unit : r722.0
200
Control_Unit : p2201
Control_Unit : r755[0]
600
-50
1.1
35
20
50
Control_Unit : r722.1
[1] Fixed speed setpoint 15 (p1015)
71.34
200
356.72
0
Last Revised: 4/11/2011
Unit
ms
rpm
rpm
%
Pa
Pa
Pa
s
%
%
%
Pa
Pa
%