Siemens SIPLUS RIC IEC on S7 Manual - Página 15
Procurar online ou descarregar pdf Manual para Equipamento industrial Siemens SIPLUS RIC IEC on S7. Siemens SIPLUS RIC IEC on S7 28 páginas. Addon nodal blocks version v1.5
TwoC_15_13_11_9_7_5_3_1
Threshold_Val_ME
FB_RetVal
IM_DB_No
No_used_IMs
New_Image
NOTICE!
Please note the permissible valuation of the block parameters. They are not mandatory
checked for plausibility. Incorrect inputs can cause unpredictable responses and incor-
rect functions.
SIPLUS RIC IEC on S7 V1.5
Functional description
Serves for fixing which TK's are transmitted also without change of the value or sta-
tus.
Set bits cause the transfer of the allocated information types also without change of
the value or status if the information was received with COT<20.
The numbers in the parameter name respond to the basis TK (without time).
Allocation of the parameter bits to the TK's
Bit
Bit 7
Bit 6
TK
15
13
Type
IT
MEc
Def.
0
0
With the default adjustment (B#16#0) only information with change of value or status
are transferred.
The nodal block offers the possibility for stabilization of measured values using
threshold procedure.
0: without any change of the measurands leads to forwarding.
>0 (e.g. 20): This value is used for direct or mathematical reachable threshold
In each cycle is a check and immediately reaction on direct threshold exceeding
The threshold processing is integrating – in a 1 sec interval the measured value dif-
ference to the last transmission is added up and transmitted spontaneously with the
mathematical achievement of the threshold.
For each measured value individual thresholds can be provided in a parameter data
block if assigned.
The function block is signaling as follows:
Positive values ok
W#16#0000
ok, no fault
W#16#1000
ok, with reduced cycle (next_Info)
Negative values (16#8xxx) fault
W#16#8102:
P_from_SL_Org = 0
W#16#8103:
Shared.Version (Job-ID) = wrong or
pointer wrong positioned
W#16#8112:
P_from_Application = 0
W#16#8113:
Application.Version (Job-ID) = wrong or
pointer wrong positioned
W#16#8301
IM-DB could not be installed
Reason could be insufficient working memory
W#16#8302
Image-DB full
Info could not be entered anymore
Number of the image-DB created from this block.
Number of the actually entered information in the image-DB.
The update of the image-DB is carried out automatically by incoming spontaneous,
requested or cyclic information.
Indicates that the number of information in the image-DB has been increased within
this OB1-cycle.