Siemens SIPROTEC T103 Manual - Página 11

Procurar online ou descarregar pdf Manual para Equipamento industrial Siemens SIPROTEC T103. Siemens SIPROTEC T103 38 páginas.

Siemens SIPROTEC T103 Manual
1.2

Commands

1.2.1

Single Commands

Reference
1.2.2

Changing The Setting Group

Reference
7VU68x Redundant T103 Bus mapping
C53000-L2540-C558-1
The annunciation "DataStop" (Obj.- Adr. 16) signals the activation of "Stop data trans-
mission" however and can be evaluated correspondingly in the IEC 60870-5-103 mas-
ter.
Note
The allocation of the output relays to the switching devices and to the binary outputs
is defined during parametrization of the SIPROTEC
Depending on the device composition there may be less than the indicated output re-
lays (and corresponding IEC 60870-5-103 Information numbers) available in the
®
SIPROTEC
device.
The command output mode (pulse output, continuous output) is changeable for the
single commands using parametrization software DIGSI
The switching direction OFF for single commands with pulse output is not permitted
and is rejected in the SIPROTEC
ref. to chap. 3.1.1
Switching on one setting group automatically switches off the current active setting
group. Transmission of the value OFF is insignificant for the change of the setting
group and is refused by the device.
A change of the setting group is only possible via IEC 60870-5-103 if the parameter
C
A
S
HANGE TO
NOTHER
tocol".
Refer to chapter 3.1.1 to the command for changing the setting group. The indication
for a change of a setting group is shown in chapter 3.2.3
®
device.
G
(parameter address = 302) has the value "Pro-
ETTING
ROUP
Notes to SIPROTEC
®
devices.
®
4.
®
objects
11