Siemens 125-5033 Manual do Proprietário - Página 29
Procurar online ou descarregar pdf Manual do Proprietário para Controlador Siemens 125-5033. Siemens 125-5033 35 páginas. Two-state constant volume fume hood controller
Safety Features
The controller board stores the controller's address, applications, and point values. In the
event of a power failure or a reset, these values are retrieved from the controller's permanent
memory and are used by the controller unless overridden by a field panel.
Controller LEDs
To determine if the controller is powered up and working, verify that the Basic Sanity Test
(BST) Light Emitting Diode (LED) is flashing ON/OFF once per second. The controller
contains six LEDs located on the circuit board. See the Controller LED lndicators section of
Chapter 1, Product Overview for more information about LEDs.
NOTE:
Siemens Building Technologies, Inc.
The TX and RX LEDs indicate communication over the FLN.
Troubleshooting
21