Operation
Keys
Description
1 ... 4
Operating access code input (level 2, programming, system test, etc.)
5
Silence / Restart sounders by successive pressing:
1st pressing:
–
2nd pressing:
–
–
3rd pressing:
Operating access level required = level 2 (silence sounders is not possible during pre-warning time)
6
Silence buzzer
Operating access level required = level 1 or 2 or 2 only (*)
7
1) Reset of the system. Reset is not possible :
during pre-warning time, emergency stop and flooding time
–
if buzzer and/or sounders are not silenced
–
–
if manual release button and/or discharged contact are not reset (*)
Operating access level required = level 2
2) Fault reset (*)
Operating access level required = level 2
8
Mode of operating, by successive pressing:
–
1st pressing:
2nd pressing:
–
3rd pressing:
–
Operating access level required = level 2
9
Led and buzzer test (duration = 6 seconds) :
All led indicators are activated and the buzzer sounds continuously (during the first three seconds, all the segments of
the display are activated, then the SW version is displayed)
Operating access level required = level 1
10
Disable / Enable by successive pressing:
–
1st pressing:
2nd pressing:
–
–
3rd pressing:
–
4th pressing:
5th pressing:
–
Operating access level required = level 2
11
Disable / Enable by successive pressing:
–
1st pressing:
2nd pressing:
–
3rd pressing:
–
4th pressing:
–
Operating access level required = level 2
12
Disable / Enable by successive pressing (not possible in case of fault or alarm):
1st pressing:
–
2nd pressing:
–
3rd pressing:
–
Operating access level required = level 2
13
Disable / Enable by successive pressing (not possible in case of fault or alarm):
1st pressing:
–
2nd pressing:
–
–
3rd pressing:
Operating access level required = level 2
14
Disable / Enable by successive pressing (not possible in case of fault or alarm):
–
1st pressing:
–
2nd pressing:
3rd pressing:
–
Operating access level required = level 2
15
Disable / Enable by successive pressing (not possible in case of fault or alarm):
–
1st pressing:
–
2nd pressing:
–
3rd pressing:
Operating access level required = level 2
18
Building Technologies
Fire Safety
silence sounders
restart sounders
silence sounders ...
automatic blocked
automatic and manual blocked
normal mode
actuators are disabled
sounders and actuators are disabled
fire controls are disabled
all is disabled
all is enabled
RT-fault is disabled
RT-fault is enabled / RT-alarm is disabled
RT-fault and RT-alarm are disabled
all are enabled
zone 1 is disabled
zone 1 is tested
zone 1 is in normal condition
zone 2 is disabled
zone 2 is tested
zone 2 is in normal condition
zone 3 is disabled
zone 3 is tested
zone 3 is in normal condition
manual release is disabled
manual release is tested
manual release is in normal condition
A6V10257477_c_en_--
2012-06