Maintenance
6.5
Checking Remote Transmission alarm
6.6
Checking Remote Transmission fault
6.7
Alarm counter
26
Building Technologies
Fire Safety
« Fire controls » Led (21) flashes slowly
3. Press « Lamp test » key (9) to end the test before 30 seconds, if necessary
Before checking the remote transmission, ensure that activation of
extinguishing is in fact blocked, the alarm sounders and the fire
WARNING
controls are disabled and the receiving station is notified of the
imminent test.
1. Enable operating access level 2
2. Press and maintain « key 3 » on numeric keypad then press key « Silence/Re-
sound sounders » (5) within 5 seconds:
RT-alarm is enabled for 30 seconds and RT-alarm Led (23) flashes slowly
3. Press « Lamp test » key (9) to end the test before 30 seconds, if necessary
1. Enable operating access level 2,
2. Press and maintain « key 4 » on numeric keypad then press key « Silence/Re-
sound sounder » (5) within 5 seconds:
RT-fault is enabled for 30 seconds and RT-fault Led (22) flashes slowly
3. Press « Lamp test » key (9) to end the test before 30 seconds, if necessary.
1. Press simultaneously the keys "1" and "2" on the numeric keypad:
The number of alarms appears on the 4 digit-display for 5 seconds (requires
plastic cover remove for XC1001-A and XC1003-A models).
A6V10257477_c_en_--