Siemens 3KA55 Brochura - Página 29
Procurar online ou descarregar pdf Brochura para Interruptor Siemens 3KA55. Siemens 3KA55 50 páginas. Switch disconnectors and fuses
■
Benefits
For the 3KL switch disconnectors with fuse, a UL approval has
been granted in combination with the new 3NE1 ...–2 fuse
series.
■
Area of application
When SITOR semiconductor protection fuses are used in
SENTRIC NP, SENTRIC KL and 3KM switch disconnectors, a
partial reduction of the rated current of the fuse is necessary due
to the higher power loss in comparison with LV HRC fuses for line
protection. The use of SITOR semiconductor protection fuses in
switch disconnectors may at times result in current values above
the rated currents of the switches. These increased currents oc-
cur only when the switch is used with SITOR semiconductor pro-
tection fuses; they cannot be utilized when the switch is used
with standard LV HRC fuses. Details are given in the table below.
When SITOR semiconductor protection fuses of series 3NC24,
3NC84, 3NE33 and 3NE43 are used, the switching capacity of
the switch disconnectors as specified in the catalog must not be
fully utilized, as the blades of these fuses (in contrast to LV HRC
line-protection fuses) are slotted. Occasional switching of cur-
rents up to the rated currents of the fuses is permissible.
Due to the mechanical stress on the relatively long fuse blades,
3NE41 SITOR semiconductor protection fuses should be
switched only occasionally and only at zero current. If it is only
■
Selection and ordering data
For switch disconnectors
Type
Type
Permissible load cur-
rent of the SITOR
semiconductor protec-
tion fuse in the switch
disconnector
A
For SENTRIC 3NP fuse switch disconnectors
3NP35,
3NP40 1,
16
3NP50
3NP40 7
20
25
35
40
50
63
80
3NP50
3NP40 7
100
125
125 (105)
3NP52
3NP42 7
160
160
200
200 (190)
250
250 (235)
3NP53
3NP43 7
315
315
3NP53
3NP43 7
350
350
400
3NP54
3NP44 7,
450
3NP44 76
450 (425)
500 (480)
500 (465)
1) If a cyclic load is applied, it may be necessary to further reduce the cur-
rents (please inquire about precise values).
2) Values in brackets apply to the SENTRIC 3NP4 fuse switch disconnector.
* This quantity or a multiple thereof can be ordered.
Required conductor
cross-section
Cu
1)
2
mm
1.5
2.5
4
6
10
10
16
25
35
50
2)
50
70
70
95
2)
95
120
2)
120
2 × 70
2 × 70
2 × 95
2 × 95
2 × 95
2 × 120
2)
2 × 120
2)
2 × 120
2)
2 × 120
Fuses and Fuse Systems
permissible to switch at zero current, the switch must be marked
accordingly.
The use of SITOR semiconductor protection fuses rated above
63 A for overload protection is also not permitted when gR fuses
(except 3NE1) are used.
The operating voltage is limited by the rated voltage of the
switch disconnector or the fuses. During current-free switching,
the limit value is the rated insulation voltage of the switch discon-
nector.
The 3NE1 "double protection fuses" can be used both as all-
range fuses (gR/gS) as well as for semiconductor and line pro-
tection.
Due to the dimensions of SITOR semiconductor protection
fuses, only the fuses shown in the Selection and ordering data
below can be used in the SENTRIC NP, SENTRIC KL and 3KM
switch disconnectors.
SITOR semiconductor protection fuse
Size
Opera-
Rated
Rated
tional
current
voltage
class
A
V
000
gR/gS
16
690
gR/gS
20
gR/gS
25
gR/gS
35
gR/gS
40
690
gR/gS
50
gR/gS
63
gR/gS
80
00
gR/gS
100
690
gR/gS
125
gR
125
1
gR/gS
160
690
gR
160
gR/gS
200
gR
200
gR/gS
250
gR
250
2
gR/gS
315
gR
315
2
gR/gS
350
690
2
gR
350
gR/gS
400
gR/gS
450
gR
450
gR/gS
500
gR
500
Introduction
DT
Order No.
PS*
Weight
per PU
approx.
kg
}
3NE1 813-0
9 units
0.127
}
3NE1 814-0
9 units
0.128
}
3NE1 815-0
9 units
0.127
}
3NE1 803-0
9 units
0.128
}
3NE1 802-0
9 units
0.127
}
3NE1 817-0
9 units
0.128
}
3NE1 818-0
9 units
0.128
}
3NE1 820-0
9 units
0.129
}
3NE1 021-0
3 units
0.202
}
3NE1 022-0
3 units
0.202
}
3NE1 022-2
3 units
0.203
}
3NE1 224-0
3 units
0.580
}
3NE1 224-2
3 units
0.613
}
3NE1 225-0
3 units
0.582
}
3NE1 225-2
3 units
0.612
}
3NE1 227-0
3 units
0.580
}
3NE1 227-2
3 units
0.626
}
3NE1 230-0
3 units
0.581
}
3NE1 230-2
3 units
0.615
}
3NE1 331-0
3 units
0.766
}
3NE1 331-2
3 units
0.754
}
3NE1 332-0
3 units
0.743
}
3NE1 333-0
3 units
0.760
}
3NE1 333-2
3 units
0.768
}
3NE1 334-0
3 units
0.766
}
3NE1 334-2
3 units
0.768
Siemens LV 10 · 2004
7/29
7