5.4.8

Speed of response

The speed of response adjustment allows the user to collectively set a number of operating
parameters.
Measurement response
Agitator discrimination
Filter
Fail-safe timer
SP
1
2*
3
4
*Factory setting
Pointek ULS200
Operating Instructions, 01/2019, A5E32268616-AB
Measurement
Agitator discrimi-
response
nation
0.3 m/min.
On
(0.1 ft/min.)
1 m/min.
On
(3.3 ft/min.)
5 m/min.
On
(16.4 ft/min.)
Immediate
Off
Is the limit to which the device is able to keep up
with rates of change.
If the device measurement cannot keep up with
the rate of level change, set the adjustment from
1 to 2. If the device still cannot keep up with the
rate of level change, set the adjustment option to
3. Avoid choosing an option that is too fast for
your application.
Discriminates between agitator blades in motion
and the material (target) surface.
Discriminates between false echoes from acous-
tical and electrical noise and the material (target)
surface.
Establishes the `Waiting' period from the time a
loss of echo or operating fault condition starts
until the fail-safe default is effected.
Filter
On
On
On
Off
FLS timer
10 min.
10 min.
3 min.
3 min.