Siemens UP 246 Informações técnicas sobre o produto - Página 4

Procurar online ou descarregar pdf Informações técnicas sobre o produto para Interruptor Siemens UP 246. Siemens UP 246 7 páginas. Pushbutton single/double/quadruple

GAMMA instabus
Technical Product Information
March 2008
DELTA profil
Pushbutton single
Pushbutton double
Pushbutton quadruple UP 245,
DELTA style
Pushbutton single
Pushbutton double
Pushbutton quadruple UP 287,

Installation instructions

• The device can be used for permanent interior instal-
lations, in dry rooms and for insertion in flush-type
boxes.
V
DANGER
• The device may only be installed and commissioned
by an authorized electrician.
• The device may not be inserted in the same box as
230 V devices.
• The device may be used in switch sockets, if VDE
approved devices have been used.
• The prevailing safety and accident regulations must
be observed.
• The device may not be opened.
• For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.

Technical data

Power supply
• via the flush-mounted bus coupler
Operating elements
• 1, 2 or 4 pairs of rockers, idle in the middle position
• Number of switching cycles: > 20,000
Display elements
per pair of pushbuttons 1 LED red for status display
e.g. pushbutton quadruple = 4 LEDs
• 1 LED red for orientation light
Connections
• 10-pole plug connector (PEI): for connection to the
flush-mounted bus coupler
Technical Manual
Update: http://www.siemens.de/gamma
2.16.1.5/4
UP 241,
neutral
UP 242,
with I/O symbols
UP 243,
neutral
UP 244,
with I/O symbols
neutral
UP 246,
with I/O symbols
UP 285,
neutral
UP 286,
neutral
neutral
Mechanical data
• Housing: plastic
• Dimensions:
• Weight: approx. 40 g
• Fire load: approx. 950 kJ ± 10 %
• Mounting: placed on the flush-mounted bus coupler
Electrical safety
• Degree of pollution (according to IEC 60664-2): 2
• Type of protection (according to EN 60529): IP 20
• Protection class (according to IEC 61140): III
• Overvoltage category (according to IEC 60664-1): III
• Bus: safety extra-low voltage SELV DC 24 V
• Device complies with EN 50090-2-2 and
Reliability
• Rate of failure: 27 fit at 40
EMC requirements
• complies with EN 50081-1, EN 61000-6-2 and
Environmental conditions
• Climatic withstand capability: EN 50090-2-2
• Ambient operating temperature: - 5 ... + 45 °C
• Storage temperature: - 25 ... + 70 °C
• Relative humidity (not condensing): 5 % to 93 %
Markings
• KNX / EIB
CE mark
• in accordance with the EMC guideline (residential and
UP 24x-28x_Taster, 7 pages
© Siemens AG 200
Subject to change without prior notice
- DELTA profil (L x W x D ): 65 x 65 x 11 mm
- DELTA style (L x W x D ): 68 x 68 x 14 mm
IEC 60664-1: 1992
EN 50090-2-2
functional buildings) and the low voltage guideline
P.O. Box 10 09 53, D-93009 Regensburg
5WG1 241-2AB_1
5WG1 242-2AB_1
5WG1 243-2AB_1
5WG1 244-2AB_1
5WG1 245-2AB_1
5WG1 246-2AB_1
5WG1 285-2AB_1
5WG1 286-2AB_1
5WG1 287-2AB_1
C
o
Siemens AG
Automation and Drives Group
Electrical Installation Technology