Actulux 111740 Manual - Página 14
Procurar online ou descarregar pdf Manual para Acessórios Actulux 111740. Actulux 111740 20 páginas.
Current Limiter and Overload Unit
ADVANCED ELECTRONIC CURRENT LIMITER
LIP7 is an advanced electronic product that is used as current
limiter and overload unit between a 24 -36 - 48 VDC supply and
for 1 actuator (motor).
When setting for the current limiter is reached because of the
actuator load, and the load on the actuator is further increased,
then the actuator speed is automatically reduced, so that the
current consumption does not exceed the set level.
A heat resistant silicone cable is mounted as supply line.
LIP7 is available in 3 versions:
LIP7 Basis, LIP7 Tandem and LIP7 Open / Close.
LIP7 BASIS
#121305
1 channel actuator protector - replaces LIP5.
CONNECTION AND SETTINGS
DIP switch
off
1
4A / 24VDC
2
3
4
5
6
7
8
(*) Please note that the above power settings are standard - can also be customized to specific Actulux actuator types
FEATURES
Power supply: 24 - 36 - 48 VDC +/- 15%, Max. Ripple: 2 Volt PP
Input resistance: Using switch on the PCB a 27kΩ resistor can be engaged
over the input terminals of the supply to the line monitoring
Max. power in the position relay: 30 VDC / 2A
Size (l x w x h): 100 x 100 x 50 mm
Material: White plastic box
Compatible with previous LIP editions
Density: IP54
Silicone cable length: Standard 85 cm
Meets requirements: EN12101-2 / EN60335-1 / EN50130-4 Marking: CE
Product number: 121305 (Basis) / 121306 (Tandem) / 121308 (OC Open / Close)
14
intelligent and electronic current limiter
LIP7 BA (basis) #121305
on
Function
Max. average current.
(Please note this is only an example - may
vary in diff. types of Opening Systems)
OFF = No 27kΩ for line detection
↓
Only available in LIP7 TA and LIP7 OC
OFF = Stand Alone mode (only 1 system / LIP)
OFF = Slave
OFF = Sync mode = 3 wire actuator (motor)
OFF = No delay between Master and Slave
Not in use
- Type LIP7
LIP7 TA (tandem) #121306
LIP7 TANDEM
#121306
1 channel but now with the opportunity to operate in
Tandem / Synchro mode with another LIP7 if 2 pcs. of opening
systems are mounted in the same window or skylight to prevent
damage to the window or skylight. The system stops if power to
one motor disappears.
There is also an opportunity to operate in Synchro mode where
both systems are running exactly with the same speed without
delay.
Synchro mode requires that the electrical actuators in the opening
system is mounted with "reed switches" for speed / position
indication.
LIP7 OPEN/CLOSE
#121308
Same features as the LIP Tandem but also with clamps for
Open / Close indication of the window or skylight.
Open / Close indication and Synchro mode requires that the
electrical actuators in the opening system is mounted with "reed
switches" for speed / position indication
OFF
24V
2A
36V
1.5A
48V
1A
OFF
ON = 27kΩ for 2 wire line detection (terminal 1 and 2)
↓
ON = Communication mode (set ON in both systems / LIPs)
ON = Master (set ON only in one system / LIP)
ON = Tandem mode = 2 wire actuator (motor)
ON = 7 seconds delay between Master and Slave
LIP7 OC (open / close) #121308
.
Settings*
ON
ON
OFF
3A
2,5A
4A
2.25A
1.9A
3A
1.5A
1,25A
2A
OFF
ON
ON