Argina CM+ Manual de instruções de instalação - Página 4

Procurar online ou descarregar pdf Manual de instruções de instalação para Unidade de controlo Argina CM+. Argina CM+ 20 páginas. Conventional fire alarm control panel

2 Installation

2.1 Removing the cover

The cover can be removed without using tools.
Place your fingers under the housing between the clips and the housing and pull the lower edge
away from the housing. Gently push the cover upwards so that it comes away from the top
pivots. Carefully pull the operating panel connector out of the main PCB.
(Replacement of the cover: in reverse order; do not forget to place the screw)

2.2 Installing the housing

Install the housing at eye level and in an easily-accessible location.
The housing must not be installed where there is a risk of it being splashed or soaked with water
The ambient temperature in the location must be between -5 °C and 40 °C, with a relative
humidity of between 0 and 95% (non-condensing).
The housing must be attached to a wall that is as flat as possible, in order to prevent distortion.
Use spacers at the attachment points if the unevenness of the wall is greater than 3 mm. It will
be difficult to fit the cover to a distorted housing and the operating panel could be damaged.
Ensure there is at least 10 cm clearance around the housing to allow proper air circulation.
There is a gap of 12 mm on the wall side and an internal gap of 22 mm, allowing wiring to enter
the housing from any direction. The breakout edges at the top or bottom can be cut away before
installation if necessary, to enlarge the cable entry by 5 mm and 10 mm respectively.
Mark the positions of the holes and attach the box, using ø 4.5 or 5 mm screws.
Housing dimensions: 340mm x 266mm