Cisco Catalyst 6509 Informações técnicas - Página 4

Procurar online ou descarregar pdf Informações técnicas para Hardware de rede Cisco Catalyst 6509. Cisco Catalyst 6509 16 páginas. Catalyst 6500 series chassis and module power and heat values
Também para Cisco Catalyst 6509: Manual suplementar (3 páginas), Manual do utilizador (28 páginas), Manual de energia (4 páginas), Ficha de dados (30 páginas)

Cisco Catalyst 6509 Informações técnicas
The module power values are based on 42 VDC. Power is distributed to each slot in the chassis from the
power supply's 42 VDC output. Each module has DC-to-DC power supplies that convert the 42 VDC
into +2.5 VDC, +3.3 VDC, and +5 VDC to power the module. The 42 VDC is independent of the power
supply's input voltage, either 110 VAC or 220 VAC.
Table D-3
Table D-3
Power Requirements and Heat Dissipation—Supervisor Engines
Model Number/
Module Type
WS-X6K-SUP1A-2GE
Supervisor Engine 1A
WS-X6K-SUP1A-PFC
Supervisor Engine 1A with PFC
daughter card
WS-X6K-SUP1A-MSFC
Supervisor Engine 1A with PFC
and MSFC daughter cards
WS-X6K-SUP1A-MSFC2
Supervisor Engine 1A with PFC
and MSFC2 daughter cards
WS-X6K-S2-PFC2
Supervisor Engine 2 with PFC2
daughter card
WS-X6K-S2-MSFC2
Supervisor Engine 2 with PFC2
and MSFC2 daughter cards
WS-X6K-S2U-MSFC2
Supervisor Engine 2 with PFC2
and MSFC2 daughter
cards—Has 512 MB of DRAM
Catalyst 6500 Series Switches Installation Guide
D-4
lists the power and the heat numbers for the supervisor engines.
Module
Module
Current (A)
Power
@ 42 VDC
(Watts)
1.70
71.40
2.50
105
3.30
138.60
2.90
121.80
3.06
128.52
3.46
145.32
3.46
145.32
Appendix D
AC
DC
AC-Input
Heat Diss.
DC-Input
Power
(BTU/HR)
Power
(Watts)
(Watts)
89.25
304.79
95.97
131.25
448.22
141.13
173.25
519.65
186.29
152.25
519.93
163.71
160.65
548.62
172.74
181.65
620.33
195.32
181.65
620.33
195.32
Chassis and Module Power and Heat Values
Heat Diss.
(BTU/HR)
327.73
481.96
559.18
559.07
589.91
667.03
667.03
OL-5781-08