Cisco APIC M4 Manual de instalação e serviço - Página 40
Procurar online ou descarregar pdf Manual de instalação e serviço para Servidor Cisco APIC M4. Cisco APIC M4 46 páginas.
Server Specifications
Table 5: Physical Specifications
Description
Temperature, Operating
Temperature, non-operating
(when the server is stored or transported)
Extended Operating Temperature
Humidity (RH), operating
Humidity (RH), non-operating
(when the server is stored or transported)
Altitude, operating
Altitude, non-operating
(when the server is stored or transported)
Cisco APIC M4/L4 Server Installation and Service Guide
36
Specification
10° C to 35° C (50° F to 95° F) with no direct sunlight
Derate the maximum temperature by 1°C per every 300 meters of altitude above
sea level.
Although the ASHRAE guidelines define multiple classes with different
Note
operating ranges, the recommended temperature and humidity operating
range is the same for each class. The recommended temperature and
humidity ranges are:
• Operating Temperature: 64.4°F to 80.6°F (18°C to 27°C)
For general information, see the
Planning Guide: Data Center Power and
Below -40° C or above 65° C (below -40° F or above 149° F)
Maximum rate of change (operating and non-operating) 20° C/hr (36° F/hr)
5° C to 40° C (41° F to 104° F) with no direct sunlight
Maximum allowable operating temperature derated
1° C/175 m (1° F/319 ft) above 950 m (3117 ft)
5° C to 45° C (41° F to 113° F) with no direct sunlight
Maximum allowable operating temperature derated
1° C/125 m (1° F/228 ft) above 950 m (3117 ft)
System performance may be impacted when operating in the
extended operating temperature range.
Operation above 40° C is limited to less than 1% of annual
operating hours.
Hardware configuration limits apply to extended operating temperature range.
8 to 90% and 24° C (75o F) maximum dew-point temperature, non-condensing
environment
Below 5% or above 95% and 33o C (91o F) maximum dew-point temperature,
non-condensing environment
0 to 10,000 feet
0 to 40,000 feet
Server Specifications
Cisco Unified Computing System Site
Cooling.