Acuity Brands Synergy LIRO H Instruções de instalação

Procurar online ou descarregar pdf Instruções de instalação para Acessórios Acuity Brands Synergy LIRO H. Acuity Brands Synergy LIRO H 2 páginas. Infrared ceiling mounted occupancy sensor, to be used with 24vdc lpcs series power pack class ii low-voltage wiring

1335 Industrial Boulevard, Conyers, GA 30012 Ph. 800-533-2719
CDCS000281
DI-400-OSC15-00A-X1
WARNINGS AND CAUTIONS:
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult a qualified electrician.
• Sensors must be mounted on a vibration free surface.
• All sensors must be mounted at least 6 feet away from air vents.
• Do not touch the surface of the lens. Clean outer surface with a damp cloth only.
Tools needed to install your Sensor:
Slotted/Phillips Screwdriver
Electrical Tape
Pliers
Pencil
Cutters
Parts Included List:
S
e
n
s
o
( r
) 1
T
h
e r
a
d
e
d
R
o
d
(
) 1
a
n
d
H
e
x
N
u
#8-32 x 1/2" Screw (2)
Half Mask (1)
#8-32 x 1-1/2" Screw (2)
360° Perforated Mask (1)
#8-32 Washer and Nut (2)
Plastic Washer (1)
DESCRIPTION
The Occupancy Sensor is a low-voltage infrared sensor that works with the LPCS Series
power pack to automatically control lighting. The sensor turns the lights on and keeps
them on whenever occupancy is detected and will turn them off after the 'delayed-off
time' has expired.
The sensor continually analyzes and adjusts to changing conditions. The sensor uses
the latest microprocessor-based technology which permits it to continually adjust and
optimize its performance.
Infrared motion detection gives higher false triggering immunity that yields a sensor with
excellent performance.
INSTALLING YOUR OCCUPANCY SENSOR
NOTE: Use check boxes
when Steps are completed.
WARNING:
Step 1
TO AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER
at circuit breaker or fuse and test that power is off before wiring!
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Preparing and connecting wires:
Step 2
1/2"
(1.3 cm)
Cut
(if necessary)
Strip Gage (measure
bare wire here)
Typical Installations:
Step 3
Listed are 3 typical installation options (A, B, and C). Choose one that best suits
your needs. Other methods of installation may be possible but they have not been
described here.
A. Drop Ceiling Installation (Mounting Option A):
NOTE: Use the threaded rod included.
1. Select location for mounting of sensor and proper masking for your application
(refer to Mounting Location Diagram).
2. Use the supplied threaded rod or other methods to make a hole (1/2" to 1") in the
ceiling tile just large enough to pass the body of the threaded rod through.
3. Insert the sensor wires through the flared end of the threaded rod. Position the
threaded rod to the base of the sensor.
4. Insert the flared end of the threaded rod into the opening in the bottom of the
sensor and twist to lock into place.
To be used with 24VDC LPCS Series Power Pack Class II Low-Voltage Wiring
Step 3 cont'd
5. Push the wires into the hole in the ceiling tile and insert the threaded rod until the
sensor is flush with the tile.
6. Insert wires through the hole in the included washer, then place the included
washer over the rod and screw on the included hex nut.
7. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per
WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit
( t
) 1
conductors, push firmly into appropriate wire connector. Screw connectors on
clockwise making sure that no bare conductor shows below the wire connectors.
Secure each connector with electrical tape.
8. Rotate the sensor to the desired orientation. Note that the sensor base and back
cover are keyed. To lock the device in place, ensure that the arrows are not aligned.
9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS
COMPLETE.
Mounting Option Diagram A
Occupancy Sensor Mounted to Drop Ceiling Using Threaded Rod
Low-Voltage Wires
Drop Ceiling
1" thick maximum
Nut
Threaded Rod
NOTE: Wires routed through
the Threaded Rod
B. Wallboard or Drop Ceiling Installation (Mounting Option B):
NOTE: You may use the mounting screws, nuts and washers included, or screws in
combination with commercially available wall anchors.
1. Select location for mounting of sensor and proper masking for your application
(refer to Mounting Location Diagram).
2. Make a hole in the ceiling tile or wallboard large enough to pass the wire
connections and wire nuts through (approximately 1" diameter).
3. Remove the back cover of the sensor. Hold the back cover and body of the sensor
and rotate until the two arrows line up and pull apart.
4. Install back cover of the ceiling sensor to the wallboard or drop ceiling using the
included screws, nuts and washers, or screws in combination with commercially
available wall anchors.
5. Class II Wiring: Connect low-Voltage wires from Power Pack to Sensor per
WIRING DIAGRAM as follows: Twist strands of each lead tightly and, with circuit
conductors, push firmly into appropriate wire connector. Screw connectors on
clockwise making sure that no bare conductor shows below the wire connectors.
Secure each connector with electrical tape.
6. Push wire connections through the center hole of the back cover and into the ceiling.
7. Secure the sensor body to the back cover by aligning the arrows. Lock it by
turning the sensor such that the arrows do not line up.
8. Rotate the sensor to the desired orientation.
9. Restore power at circuit breaker or fuse to Power Pack. INSTALLATION IS COMPLETE.
Mounting Option Diagram B
Occupancy Sensor Mounted to Wallboard
or Drop Ceiling Using Screws
Low-Voltage Wires
Low Voltage Wires
Nut (2 places)
Washer (2 places)
Wallboard
Ceiling
Sensor
Back Cover
Wallboard Ceiling
Mounting Screws
(2 places)
Keylock Arrow
Sensor Base
Sensor Front Cover
Infrared Ceiling Mounted Occupancy Sensor
Cat. No. LIRO H
INSTALLATION INSTRUCTIONS
CATALOG ITEMS
Current
Suggested
Catalog No.
Description
Consumption
Coverage
Mounting Location
Mount in center
LIRO H
Extended Range
20mA
1500 sq. ft.
of room/area
Step 3 cont'd
C. Junction Box or Surface Mount Raceway Installation (refer to
Mounting Diagrams):
NOTE: Listed below are suggested JUNCTION BOX installation applications which
require mounting to conduit in one of the following three ways:
Occupancy Sensor Mounted to Octagon
Box Installed Flush to Wallboard Ceiling
#8-32 Screws
(2 places)
Washer
Wallboard or
Drop Ceiling
TABLE 1: WIRE DESIGNATIONS
Name
Color
Power (+24V)
Red
DC Return
Black
Occupancy
Blue
Occupancy/Photocell
Gray
Back Cover open center to
route Low-Voltage Wires
Mounting Screw
Back Cover internal
surface shown
Back Cover shown mounted
on ceiling with screws
FCC COMPLIANCE STATEMENT:
T
his device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1)
This device must not cause harmful interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.
Step 3 cont'd
Occupancy Sensor Mounted to Round Fixture
Octagon Box
4" x 1 1/2" deep
Wire Mold Round Fixture
Box Cat. No. V5738
(for raceway mount)
Low-Voltage
Wires
Wiring Diagram 1: Multiple Sensor, Single Power Pack
LPCS Series
Power Pack
Gauge
Temp/Voltage
24
200° C/ 600V
Red (24VDC)
24
200° C/ 600V
24
200° C/ 600V
Black
Red
24
200° C/ 600V
Blue
(Control)
Black
Blue
Blue
Red
Hot (Black)
Blue
Black
Black
Blue
Line
White
120/277/347VAC
60Hz
Neutral (White)
with Raceway for Wallboard Installation
Wire Mold Back Cover
Back Cover Screws
(4 places)
Low-Voltage Wires
Mounting Screws
(4 places)
Wallboard Ceiling
Wire Mold Raceway
(use applicable fittings)
Sensor
*
NOTE: When using the
NC-Brown
To HVAC
Photocell function, connect
Common-Green
System
the Gray wire of the sensor
(DCO Only)
NO-Brown/White
to the Blue wire of the
power pack. DO NOT use
the Blue wire of sensor.
*
Gray
NOTE: Cap all unused
Black
wires.
Load
Gray
*
White