Toshiba BMS-IFMB0TLR-E Manual de instalação - Página 2
Procurar online ou descarregar pdf Manual de instalação para Ar condicionado Toshiba BMS-IFMB0TLR-E. Toshiba BMS-IFMB0TLR-E 4 páginas. Mb interface
MB Interface
Safety instructions
WARNING
Follow carefully these safety and installation instructions. Improper work may lead to serious harmful for your health and also may damage seriously the interface
and/or the Air-conditioning unit.
• This interface must be installed by accredited technical personnel (electrician, installer, or technical personnel) and following all the safety instructions.
• Before manipulating the Air-conditioning unit, be sure it is completely disconnected from Mains power.
• Do not modify the unit. (A fire or an electric shock may occur)
• This interface must only be installed in a restricted access location by user.
• Do not install the unit in any of the following places.
• Humid or wet place
• Dusty place
• Place exposed to direct sunlight
• Place where there is a TV set or radio within one meter
• Place exposed to rain (outdoors, under eaves, etc.)
• Use predefined cable and connect them certainly. Keep the connecting terminal free from external force.
It may cause an exothermic or a fire.
• Strip the insulation from the cable that connects to the connector (RS-485 and A B bus) following the dimensions shown in the diagram below.
• When connecting the cable to the connector (RS-485 and A B bus), ensure the core wires do not protrude from the connector.
• Use two-core cabtyre cable.
Installation instructions
• Disconnect the Air-conditioning from Mains Power.
• Fix the interface beside the Air-conditioning (wall mounting) following the instructions in the diagram below or install it inside the Air-conditioning (respect the
safety instructions given above).
• Connect the interface to A B bus in any point of the bus. The A B bus is the bus that connects the Air-conditioning unit, and the wired remote controller, is a two-
wire bus connecting terminals A B of both, this A B connection has no specific polarity.
• Connect the RS-485 bus to the connector RS-485 of the interface.
• Close the Air-conditioning unit and reconnect it to Mains Power.
• Follow the instructions on the user manual for configuring and commissioning the interface.
• Follow the instructions of the next page to configure the interface through on-board DIP-switches.
NOTE
The cable used for connection of BMS-IFMB0TLR-E to A B bus can be any two-core cabtyre cable, the maximum distance for bus A B is 300 meters, consult the
manual of the Air-conditioning for more details.
Respect the maximum distance of 500 meters for the bus, no loop or star topologies are allowed for RS-485 bus, a terminator resistor of 120 Ω must be present at
each end of the bus to avoid signal reflections and also a fail-safe biasing mechanism.
IMPORTANT:
• Use only one remote controller. A sub-remote controller cannot be connected when connecting this interface.
Indoor unit
NOTE
In its place there is a pair of cables to connect the Remote Controller. Use these cables to connect the AB bus. Check your Air-Conditioning user or service manual
for more information.
2
-EN
Remote Control
Internal Block in
the indoor unit.
A
B
B
A
Max. 300 m
Connection to A B bus.
Two-core cabtyre cable.
Length of stripped RS-485 and A B bus communication
cable
(20 mm)
53 mm
A
B
TOSHIBA
BMS-IFMB0TLR-E
RS-485
A+
B-
90 mm
DIN rail
Installation Manual
(5 mm)
Interface installation
• Install the
interface on the
DIN rail.
• For wall mount
extract the upper
and down
staples until you
hear the "click".
MODBUS RTU
RS-485
Bus