Only qualified service personnel shall perform installation and service.
Introduction:
These instructions list the steps required to field install a larger centrifugal blower
and ¾ HP motor assembly in any of the Crown oil-fired furnace models previously
noted. A blower upgrade kit will produce an increase in high-speed airflow to enable
the furnace to support an evaporator coil capable of producing approximately four
(4) tons of direct expansion cooling.
:
NOTICE
The blower upgrade kit is equipped with a ¾ HP, PSC-type, fan
motor. Electrical service to the furnace may have to be upgraded, in certain
situations, to support the larger motor.
Table 1: Electrical Power Supply Requirements for a Furnace Equipped w/
Total Current (A)
Minimum Circuit Ampacity (A)
Maximum Fuse Size (A)
Installation:
A. Remove the Standard Blower / Motor Assembly
! WARNING:
furnace to cool to room temperature before proceeding with disassembly.
! WARNING:
blower terminal block, use a voltmeter (or equivalent device) to measure
the electrical potential across the red and white wires and the orange and
white wires at the terminal block. No (zero) voltage readings confirm power
to the blower is off.
! CAUTION:
thermostat may interfere with easily removing the blower from the furnace.
To avoid damaging the thermostat, temporarily remove the thermostat
BEFORE removing the blower. Loosen two (2) sheet metal screws fixing
the thermostat to the blower support panel and carefully move the
thermostat to the side. Retain these fasteners for later reuse. It should not
be necessary to disconnect the electrical wiring from the thermostat.
1. Set the room thermostat operating mode to "OFF" and shutoff electrical
power to furnace at the disconnecting switch.
2. Remove the blower access panel.
Standard or Upgrade Motors
Standard ½ HP Motor
If the heating system was recently operating, allow the
BEFORE disconnecting the furnace wiring harness at the
On horizontal / counterflow models, the auxiliary high limit
10.2
12.1
15
1
Upgrade ¾ HP Motor
13.6
16.4
20