With regard to possible occurrence of electrostatic charge on non-conductive parts of the level meter for explosive areas (Xi ver-
sion) must be grounded with ground terminal!
The power supply can be a stabilized voltage supply unit of 18 ÷ 36V DC (30V DC for Xi version) that is included in evaluation or
display unit.
In case of strong electromagnetic interference (EMI), parallel supply cable with power lines, or when the cable length exceeds
30 m, we recommend you to use a shielded cable.
Always disconnect the supply voltage before connecting the level meter!
L
EVEL METER SETTING
Set the level meter using 3 buttons placed on the display module. All settings are accessible in the ULM-70 set-up mode access.
For detailed information please read at the instructions manual.
button
– Set-up mode access
– Confi rmation of selected item in the menu
– Saving of set-up data
button
– Move in the menu
– Change of values
button
– Cancelling of carried out changes
– Shift one level up
* Slow fl ashing while the refl ected signal (echo) is received from the measured level.
R
ANGE OF APPLICATIONS
For continuous non-contact level measurement of liquids (water solutions, sewerage water, etc.), mash and paste materials (sedi-
ments, sticks, resins etc.) in closed or open vessels, sumps, reservoirs and open channels. In case the level of bulk-solid materials
is measured, the measurement range is reduced. We recommend to consult the use with the manufacturer.
O
RDER CODE
ULM – 70
C
ORRECT SPECIFICATION EXAMPLES
ULM–70N–02–I
ULM–70Xi–06–I
Output type: I - current
Maximum range: 02 - 0.2 ... 2 m
Performance:
ULM–70N–10–I
ULM–70Xi–20–I
Display
of measured values
Set-up elements
Teaching
mode activation
06 - 0.25 ... 6 m
10 - 0.4 ... 10 m
20 - 0.5 ... 20 m
N - Normal - usable in non-explosive areas only
Xi - Explosion proof - suitable for explosive areas
Echo receiving *
Units
ULM-70-dat-5.6