NSTALLATION
Level meter is installed into the upper lid of the tank (vessel), using a fi xing nut or a fl ange.
If installed in an open channel (sumps, reservoirs, etc.), install the level meter as closest as you can to the maximum level
expected.
The front of the level meter must be vertically to the measured level.
Foam on the level absorbs the acoustic wave refl ection which might cause malfunction of the level meter. If possible select the
location where the foaming is as low as possible.
Protect the level meter against direct sunlight.
In the case of uncertainty we recommend to consult the application with the producer.
M
OUNTING RECOMMENDATION
Recommended installation
Installation distance from the tank wall
E
LECTRICAL CONNECTION
The ultrasonic level meter is designed to be connected to supply unit or to
controller through a cable with the outer diameter of 6 ÷ 8 mm (recommended
cross-section of cores 0.5-
0.75 mm
2
) by means of bolted
clips placed under display
module. Connect the plus
pole (+U) to the terminal "+",
the minus pole to 0V to the
terminal "-" and the shielding
to the terminal " " (only for
shielded cables).
c - measuring range
d - min. distance from tank wall
d > 1/12 c
ULM–70_–02; 10–I
(min. 200 mm)
d > 1/8 c
ULM–70_–06–I
(min. 200 mm)
d > 1/10 c
ULM–70_–20–I
(min. 200 mm)
Connection diagram of the level meter
a < 3 b
ULM–70_–02; 06–I
b > 100 mm
a < 1,5 b
ULM–70_–10–I
b > 100 mm
a < 1,5 b
ULM–70_–20–I
b > 150 mm
a - neck height
b - neck width
m - dead zone
Possible installation through the neck
m - dead zone
Maximum level distance from ULM
Metal clip
Internal view of terminal block
Display unit
connector
Terminal
block