Ariston Velis Evo 45L Manual de instruções de montagem e funcionamento - Página 10
Procurar online ou descarregar pdf Manual de instruções de montagem e funcionamento para Aquecedor de água Ariston Velis Evo 45L. Ariston Velis Evo 45L 25 páginas. Unvented water heater
Suggest ways of terminating discharge pipes safely
Temperature & pressure
relief valve
iv) Where a single pipe serves a number of discharges, such as in blocks of fl ats, the number served
should be limited to no more than 6 systems so that any installation can be traced reasonably easily.
The single common discharge pipe should be at least one pipe size large than the largest individual
discharge pipe to be connected. If unvented hot water storage systems are installed where discharg-
es from safety devices may not be apparent i.e. in dwellings occupied by the blind, infi rm or disabled
people, consideration should be given to the installation of an electronically operated device to warn
when discharge takes place. Note: The discharge will consist of scalding water and steam.
Asphalt, roofi ng felt and non-metallic rainwater goods may be damaged by such discharges.
Table 2
Sizing of copper discharge pipe "D2" for common temperature valve outlets
Minimum
Valve
size of
outlet size
discharge
pipe D1*
G 1/2
15 mm
G 3/4
22 mm
G 1
28 mm
10 / EN
Metal discharge pipe (D1) from
temperature & pressure relief valve.
to tundish.
600 mm Max.
300 mm
Min.
Metal discharge pipe (D2) from tundish
with continuous fall. See Table 2 and worked
example.
Minimum size of
discharge pipe
D2* from tundish
22 mm
28 mm
35 mm
28 mm
35 mm
42 mm
35 mm
42 mm
54 mm
Tundish
Maximum resistance
allowed, expressed as
a length of pipe
(i.e. no elbow or bends)
Up to 9 m
Up to 18 m
Up to 27 m
Up to 9 m
Up to 18 m
Up to 27 m
Up to 9 m
Up to 18 m
Up to 27 m
Discharge below
fixed grating.
(see page 6 for
alternative points
of discharge).
Fixed grating
Trapped gulley
Resistance created
by each elbow or
bend
0.8 m
1.0 m
1.4 m
1.0 m
1.4 m
1.7 m
1.4 m
1.7 m
2.3 m