Ariston EURO COMBI 47-116-12 Manual de instruções de instalação - Página 11

Procurar online ou descarregar pdf Manual de instruções de instalação para Caldeira Ariston EURO COMBI 47-116-12. Ariston EURO COMBI 47-116-12 28 páginas. Type c boilers

Ariston EURO COMBI 47-116-12 Manual de instruções de instalação
BC
F
D
J
HI
A
Fig. 2.5
Ø 60/100 mm
Fig. 2.6
Fig. 2.7
B023
F
G
E
K
L
G
The boiler is designed to be connected to a coaxial flue discharge system.
In addition, it is also possible to use a twin-pipe (split) system by fitting a special
adaptor to the flue discharge collar and using one of the apertures for the air
vent intake located on the top part of the combustion chamber (A).
Ø 80 mm
Ø 80 mm
TERMINAL POSITION
A - Directly below an open window or other opening
B - Below gutters, solid pipes or drain pipes
C - Below eaves
D - Below balconies or car-port roof
E - From vertical drain pipes and soil pipes
F - From internal or external corners
G - Above ground or below balcony level
H - From a surface facing a terminal
I - From a terminal facing a terminal
J - From an opening in the car port
( e.g. door, window ) into dwelling
K - Vertically from a terminal in the same wall
L - Horizontally from a terminal in the same wall
A
A
A
mm
300
75
200
200
75
300
300
600
1200
1200
1500
300
11