VOLTAGE DROP CHARTS
For best performance and lumen output, ensure proper wire gauge is installed to compensate for voltage drop of
low voltage circuits.
Example: 12V Voltage Drop & Wire Length Distance Chart
Wire
10 W
20 W
Gauge
.83 A
1.7 A
18 AWG
34 ft.
17 ft.
16 AWG
54 ft.
27 ft.
14 AWG
86 ft.
43 ft.
12 AWG
134 ft.
68 ft.
10 AWG
199 ft.
99 ft.
1
Determine load size. Let's assume load is 55W Round up to the nearest load.
2
Determine distance from driver to load. Let's assume the distance is 20ft
3
It's Recommended to install 12AWG to eliminate excess voltage drop
12V Voltage Drop & Wire Length Distance Chart
Wire
10 W
20 W
Gauge
.83 A
1.7 A
18 AWG
34 ft.
17 ft.
16 AWG
54 ft.
27 ft.
14 AWG
86 ft.
43 ft.
12 AWG
134 ft.
68 ft.
10 AWG
199 ft.
99 ft.
24V Voltage Drop & Wire Length Distance Chart
Wire
10 W
20 W
Gauge
.42 A
.83 A
18 AWG
134 ft.
68 ft.
16 AWG
215 ft.
109 ft.
14 AWG
345 ft.
174 ft.
12 AWG
539 ft.
272 ft.
10 AWG
784 ft.
397 ft.
30 W
40 W
50 W
2.5 A
3.3 A
2.1 A
11 ft.
8 ft.
6 ft.
18 ft.
13 ft.
10 ft.
29 ft.
21 ft.
17 ft.
45 ft.
34 ft.
27 ft.
66 ft.
49 ft.
39 ft.
30 W
40 W
50 W
2.5 A
3.3 A
2.1 A
11 ft.
8 ft.
6 ft.
18 ft.
13 ft.
10 ft.
29 ft.
21 ft.
17 ft.
45 ft.
34 ft.
27 ft.
66 ft.
49 ft.
39 ft.
30 W
40 W
50 W
1.3 A
1.7 A
2.1 A
45 ft.
33 ft.
27 ft.
72 ft.
54 ft.
43 ft.
115 ft.
86 ft.
69 ft.
181 ft.
135 ft.
108 ft.
263 ft.
197 ft.
158 ft.
60 W
4.2 A
5 ft.
9 ft.
14 ft.
22 ft.
33 ft.
60 W
4.2 A
5 ft.
9 ft.
14 ft.
22 ft.
33 ft.
60 W
70 W
80 W
2.5 A
2.9 A
3.3 A
22 ft.
19 ft.
17 ft.
36 ft.
31 ft.
27 ft.
57 ft.
49 ft.
43 ft.
90 ft.
77 ft.
68 ft.
131 ft.
112 ft.
98 ft.
100 W
4. 2 A
14 ft.
22 ft.
36 ft.
56 ft.
82 ft.