The Coaster can be fitted with either a 3kwt or 5kwt wetback to supplement the hot
water system.
WARNING:
DO NOT CONNECT TO AN UNVENTED HOT WATER SYSTEM.
DO NOT USE THIS FIRE WITHOUT WATER RUNNING THROUGH THE
WETBACK.
Care must be taken to protect the wetback coil and associated pipe work if being
installed in a hard/corrosive water area. Damage caused to the Wetback coil if
fitted in a hard/corrosive water area will not be covered under the
manufacturer's warranty.
INSTALL IN ACCORDANCE WITH AS 3500.4.1 OR NZS 4603 AND THE
APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING CODE OR
CODES.
For best performance apply the following rules:
1. Keep it simple with the shortest and straightest possible pipe run.
2. The heater should be within 6 metres of the hot water cylinder, the closer the
better.
3. Keep all flow pipes rising - the cylinder should be at least 300 mm above the
wet-back outlet.
4. Use only 25mm supply and return pipes.
5. Where possible the pipes should be insulated.