FirePro FPC-2V2 Manual de operação e instalação - Página 16

Procurar online ou descarregar pdf Manual de operação e instalação para Controlador FirePro FPC-2V2. FirePro FPC-2V2 19 páginas. Fire extinguishant controller

FirePro FPC-2V2 Manual de operação e instalação

6. Specifications

Mains supply
Maximum current
Fuse rating
Operating voltage
Output voltage
Standby current
Extinguishant release output
Extinguishant release
Extinguishant release duration
Detection Type
Detection Circuit End of Line
Fault monitoring
Fault relay contact rating
Fire relay contact rating
Cable entries
Terminal capacity
Overall size
Construction
Finish
Colour
Panel environmental class
Operating temperatures
Maximum relative humidity
Man-1556 Rev.02
FPC-2V2 Fire Extinguishant Controller Operation and Installation Manual
24V DC +10% - 15%
1.6 Amps
1.6 Amps (Quick Blow)
19-30VDC
19-30VDC +/- 2%
18 milliamps
19-30VDC, Fused at 1.6 Amp
Immediate – Max 4 FirePro Condensed
Aerosol Generators
Latched - Continuous
Conventional Smoke or Heat Detectors – Max of
2 Detectors, can be mixed.
Linear Heat Detection Cable - Latching Type NO
– LHD Cable Max 30m.
6K8 5% ½ Watt resistor
Detection and actuator circuits (open circuit
monitored only)
30VDC 1A Amp max
30VDC 1A Amp max
8 X 21mm knockouts
0.52mm to 2.52mm solid or stranded wire
190mm x 136.5mm x 43mm
1/2mm sheet steel
Epoxy powder coat
BS OO A 05 light grey textured
Class A and is designed for indoor use only
-5oC (+/- 3) and +40oC (+/- 2)
95%
Page 16 of 18