3. Mount the siren/strobe (P/N FP-08940) in a location where it is visible and audible in all points
with the risk area and connect to the "SIREN OUTPUT" on the module (marked orange). If more
than one siren/strobe is being installed, they are to be connected using the secondary
positive/negative terminals in the sounder.
The supplied end-of-line diode should be installed in the secondary positive/negative terminals
of the last siren/strobe in the circuit. The diode is polarised, so the positive lead of the diode
(marked with a grey band) should be terminated in the positive terminal of the siren/strobe,
otherwise a fault will occur on the fire control panel.