Whirlpool RH3736XLS3 Instruções de instalação e manual de utilização e cuidados - Página 5
Procurar online ou descarregar pdf Instruções de instalação e manual de utilização e cuidados para Campânula de ventilação Whirlpool RH3736XLS3. Whirlpool RH3736XLS3 24 páginas. 30" (76.2 cm) and 36" (91.4 cm) range hood
Também para Whirlpool RH3736XLS3: Lista de peças (1 páginas)
• Donot t erminate thevent s ystem inanattic orother e nclosed
area.
• Donotused a4"(10.2 cm) l aundry-type
wall c ap.
• Use a7"(17.8 cm) o ra31/4" x10"(8.3 x25.4 cm) r ound metal
vent. R igid metal vent i srecommended.
Plastic o rmetal foil
vent i snotrecommended.
• The length o fvent s ystem andnumber ofelbows s hould be
kept t oaminimum t oprovide e fficient performance.
For the most efficient and quiet operation:
•
Use no more than three 90 ° elbows.
•
Make sure there is a minimum of 24" (61 cm) of straight vent
between the elbows if more than 1 elbow is used.
•
Do not install 2 elbows together.
•
Use clamps to seal all joints in the vent system.
•
The vent system must have a damper. If roof or wall cap has a
damper, do not use damper supplied with the range hood.
•
Use caulking to seal exterior wall or roof opening around the
cap.
Vent system must terminate to the outdoors, except for non-
vented (recirculating) installations.
Roof Venting
A
....
Cold weather
installations
An additional back draft damper should be installed to minimize
backward cold airflow and a thermal break should be installed to
minimize conduction of outside temperatures
as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Wall Venting
!
C
C
A. 7" (17. 8 cm) round vent or a
3V4" x 10" (8,3x25.4
cm) vent
through roof
B. Round vent: use 7" (17.8 cm)
round damper
(purchased separately)
C. 24" (61 cm) to 30" (76.2 cm)
above cooking surface
D. Roof cap
A, 7" (17.8 cm) round vent ora
3V4" x 10" (8.3 x 25.4 cm) vent
through the wall
B. 3V4" x !0" (8.3 x 25.4 cm)
through the wall
C. 24" (61 cm) to 30" (76.2 cm)
above cooking surface
D. Wall cap
Calculating
Vent System
Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
7" (17.8 cm) Vent System
Vent Piece
7" (17.8 cm) Round
Makeup
air
Local building codes may require the use of make up air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
45 ° elbow
2.5 ft
(o.8m)
90 ° elbow
5.0 ft
(1.5m)
Vent system can terminate either through the roof or wall. Use
31/4 '' x 10" (8.3 x 25.4 cm) with a maximum vent length of
35 ft (10.7 m) or 7" (17.8 cm) round vent with a maximum length
of 50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended.
Flexible vent creates
back pressure and air turbulence that gently reduces
performance.
7" (17.8 cm)
0.0 ft
wall cap
(0.0 m)
3V4" x 10" (8.3 cm x 25.4 cm)
4.5ft
to 7" (17.8 cm)
(1.4 m)
3V4" x 10" (8.3 cm x 25.4 cm)
5.0ft
to 7" (17.8 cm) 90 ° elbow
(1.5 m)