ELECTRICAL REQUIREMENTS
To ensure you will have an opportunity to use your spa soon after delivery, it is very important that the required electrical
service has been installed. Unless otherwise stipulated by your dealer, THIS IS YOUR RESPONSIBILITY.
IMPORTANT: All electrical circuits must be installed by a qualified, licensed electrician.
** Refer to NEC 250-122 (table)
** Refer to NEC 250-122 (table)
NOTE: The wire connections to GFCI breakers are for reference only. Always ensure the white neutral wire is connected to the load neutral of the 30 amp breaker.
*PROVIDED WITH SPA.
230 V
I
OLT
NSTALLATION
Your spa contains a control box designed to operate at 230V, 60Hz. Installation of a 50 amp. dedicated circuit is
recommended. The control box must be hard wired directly to a
subpanel protected by a Ground Fault Circuit Interrupter (GFCI).
The subpanel containing GFCI breakers is included with the spa.
IMPORTANT NOTE: All electrical connections to the control box
must be accomplished by a qualified electrician in accordance with
the National Electrical Code and in accordance with any local
electrical codes in effect at the time and place of installation.
All electrical connections must be made in accordance with the
wiring information contained in this manual and on the back of the
field wiring access panel of the control box. A licensed electrician
should install a four-wire electrical service (two line voltages, one
neutral, one ground) from the main electrical service panel to the
subpanel. The equipment pack requires a MINIMUM of 112 volts
per line under load.
The grounding conductor must be at least #10 AWG. Your electrician should mount the subpanel in the vicinity of the spa
but it should not be closer than five (5) feet from the spa water edge (NEC 680-38 to 41-A-3).
INSTALLATION NOTE: After the spa has been installed, your electrician can connect the conduit from the subpanel to
the spa's control box and then complete the wiring connections in the control box.
NOTE: Complete step-by-step Installation and Wiring Instructions for all models are included in the Owner's Manual
and with each sub-panel, which can be obtained from your dealer.
WARNING: Removing or bypassing the GFCI breakers in the subpanel at any time will result in an unsafe spa and will
void the warranty.
230 Volt Permanently Connected
WARNING!
THE EXACT PHYSICAL LOCATION OF THE TERMINALS ON THE GFCI BREAKER
WILL VARY BETWEEN MANUFACTURERS. CONNECTING THE HOT WIRE TO THE
NEUTRAL TERMINAL WILL CAUSE IRREVERSIBLE DAMAGE TO THE CONTROL BOX.
** **
NOTE: ALL WIRING SHOULD BE COPPER.
GRD
System Ground Terminal
POWER CONNECTION ACCESS
CONTROL BOX
230V WIRING ACCESS
OPENINGS ON RIGHT& LEFT HAND SIDE
DOOR
Page 11