FRONT PANEL INDICATORS

1. FAULT / TEST / DISABLE - COMMON - yellow led - illuminates when any fault with the panel has
occurred, the specific fault led is flashed. If no other fault led is on, it indicates the monitored input is in
fault.
2. FIRE- COMMON - red led – illuminates during a fire / evacuation condition or if set up, it illuminates
when class change is activated.
3. ZONE 1-8 FIRE - red led's - Illuminates when a fire occurs on the relevant zone. The COMMON
FIRE led will also be illuminated at the same time.
4. ZONE 1-8 FAULT - yellow led's – Flashes (slowly) the relevant zone led during a fault condition.
Illuminated (steady) to indicate it is disabled or when in walktest is quickly flashed.
5. SUPPLY - green led - Illuminated whilst there is power (mains/battery) available to the panel.
6. SUPPLY FAULT - yellow led – Flashes when a power supply fault has occurred. Check mains and
battery.
7. DISABLED - yellow led - illuminates when a fire zone and or alarm has been disabled, the relevant
zone and or alarm fault led is illuminated - steady.
8. ALARM FAULT/DISABLED - yellow led – Flashes when the panel detects a fault with the sounder
wiring. Common fault led is also illuminated.
It is illuminated when the alarms are disabled along with the DISABLED led.
9. ALARM SILENCED - yellow led – Illuminates when the sounders on the alarm circuits have been
switched off during a fire/evacuation – The alarm condition still remains.
10. TEST - yellow led - illuminates when walk test function is selected.
11. EARTH FAULT - yellow led - Flashes if a fault with the earthing of the system has occurred.
12. SYSTEM FAULT - yellow led – Illuminates if the panel has been restarted by the supervisory circuit.
Flashes if an error in the system software has been detected – Requires attention.
13. DELAY ENABLED - yellow led – illuminates when there is a delay to the sounders activating.