CALECTRO Uniguard Superflow UG3-A-SENSE Instruções de instalação - Página 4
Procurar online ou descarregar pdf Instruções de instalação para Acessórios CALECTRO Uniguard Superflow UG3-A-SENSE. CALECTRO Uniguard Superflow UG3-A-SENSE 4 páginas.
Montering vid risk för kondensproblem,
t.ex. kallvind eller utomhus.
Extern LED som
larmindikering.
Remote LED
indication.
Håltagning Ø 38 mm.
Drill a hole Ø 38 mm.
UG-beslag, rund eller isolerad plan kanal.
Med hjälp av beslaget kan kanal-
diametern vara så liten som 100 mm.
UG-beslaget levereras plant.
The UG-bracket is supplied flat.
UG-beslaget är lätt att böja/forma så att det
passar runda eller plana kanaler.
The UG-bracket can easily be bent or
shaped to fit circular or rectangular duct.
SLUTKONTROLL
• Kontrollera att riktningspilarna pekar i flödesriktningen.
• Kontrollera att pluggen till testhålet sitter i ordentligt.
• Kontrollera att flödesindikatorn visar på flöde (vippar).
!
Enligt WEEE (Waste of Electrical and Electronic Equipment)
direktiv, skall produkten när den är förbrukad lämnas separat hos
ett härför avsett insamlingsställe och inte placeras bland osorterat
avfall. Alternativt returnera den till Calectro för återvinning.
DOLD rökdetektor
HIDDEN smoke detector
Skylt
Sign
Isolermatta 100-200 mm används för att
täcka hela Uniguarden vid montering
på kallvind. Anvisningsskylt bör monteras.
Use insulation cover of 100-200 mm and
protect the entire Uniguard. A sign should
be used to show location of the detector.
Håltagning
Ø 51 mm.
Drill a hole
Ø 51 mm.
Mounting in places where possible
9
condensation problems could arise, e.g.
cold attics or outdoor.
Håltagning Ø 38 mm.
Drill a hole Ø 38 mm.
UG-bracket for circular or insulated
10
rectangular ducts.
Using the UG-bracket the diameter of
the duct can be as small as 100 mm.
Fäst beslagets
ben på kanalen.
Fix the bracket
on to the duct.
Gummi-
tätning.
Rubber
gasket.
Rund kanal.
Circular duct.
• Check that the air flow direction arrows have the same direction
as the air flow in the duct.
• Check that the plastic plug of the test hole is properly mounted.
• Check that the flow indicator oscillates ensuring proper air flow
through the detector.
According to WEEE (Waste of Electrical and Electronic Equipment)
directive, you must at the end of life of the product dispose of it
separately at an appropriate collection point and not place it with
unsorted waste. Alternatively return it to Calectro for recycling.
Vid montering i kanal utomhus används
isolerande skyddshuv/låda UG-COVER.
For outdoor location use protection
cover e.g. Calectro´s UG-COVER.
Gummi-
tätning.
Rubber
gasket.
Isolerad, plan kanal.
Insulated rectangular duct.
FINAL CHECKS
!