TO COMMISSION INDIRECT HIGH PRESSURE
FIRETRACE SYSTEMS
Warning Firetrace
CO2 & N2 cylinders contain high pressure .Proceed with caution.
Do not turn valve FT0117/1 until system is fully commissioned.
Do not remove outlet blanking cap until cylinder is properly secured.
This procedure should be read in conjunction with document 013 basic design layout for
Indirect High Pressure systems.
Do not turn valve FT0117/1 until system is fully commissioned
Locate cylinder and firmly secure with bracket provided
Connect Trace detection tube, tighten silver nuts and secure with appropriate clips
Remove gauge FT0107/1 from end of line gauge adapter FT0118/1
Fit Schrader adapter FT0172 and pressurise to 17 Bar / 245 psi using a Nitrogen cylinder or
air pump
Remove Schrader adapter FT0172 and refit gauge FT0107
Check gauge is reading mid-green and
leave system for a minimum of ten minutes per
metre of Trace detection tube to check for leaks on the Trace detection tubing.
Install FT0184 8mm diffuser pipework, connect to cylinder using FT0167 Adaptor. When
installation is complete, disconnect FT0167 from cylinder and fit blank cap
When satisfied pressure is good and no leaks have occurred open Isolate valve FT0117 slowly.
CLOSED
OPEN
Remove blank cap and reconnect FT0184 8mm discharge pipework.
System is now live
Optional FT0124 pressure switch can be fitted in spare gauge adapter on head assembly or at
end of line
Please note system will not operate with isolate valve
in closed position
P a g e
| 12