status of command outputs,
MON0025
25
represented with an 8-bit
status of inputs, represented
MON0027
27
with an 8-bit integer.
number of cleaning cycles
MON0030
30
performed by the device, repre-
sented with a 16-bit integer
alarm code present on device,
MON0031
31
represented with an integer
PA0000
1000
Current day (from 1 to 31).
PA0001
1001
Current month (from 1 to 12).
PA0002
1002
Current year (from 18 to 99).
PA0003
1003
PA0004
1004
Device communication config-
PA0005
1005
PA0006
1006
Language selection
1
integer.
1
1
1
1
1
1
Current time.
1
Current minutes.
1
1
uration bit.
1
0
0
0
0
1
1
1
31
1
1
1
12
1
18
18
99
1
0
0
23
1
0
0
59
1
0x00
0x03
0xFFFF
1
0x00
0x00
0x03
12
Bit 0: motor command
Bit: 1 drain valve command
Bit: 2 domestic water valve command
Bit: 3 inlet valve command
Bit: 4 cooling output command
Bit: 5 inhibition output command
Bit: 6 alarm output command
Bit: 7 voltage free output command
Bit: 0 inhibition input status
Alarm identification code:
1: low pressure alarm on sensor 1
2: low pressing alarm on sensor 2
3: leakage alarm
4: seepage alarm
5: inlet valve blocked alarm
7: drain valve blocked open alarm
8: drain valve blocked closed alarm
10: error, communication with sensor 1
not possible
12: error, communication with sensor 2
not possible
13 : domestic water low pressure alarm
14: air vent blocked alarm
15: sensor 1 clip break alarm
16: sensor 2 clip break alarm
20: sensor 1 pressure measurement
error
21: sensor 1 pressure measurement
over range error
22: sensor 1 pressure measurement
under range error
23: sensor 1 temperature measurement
error
24: sensor 1 temperature measurement
over range error
25: sensor 1 temperature measurement
under range error
26: sensor 2 pressure measurement
error
27: sensor 2 pressure measurement
over range error
28: sensor 2 pressure measurement
under range error
29: sensor 2 temperature measurement
error
30: sensor 2 temperature measurement
over range error
31: sensor 2 temperature measurement
under range error
bit 0 : enable communication with
MODBUS protocol
0 = communication not enabled
bit 1 = communication enabled
bit 1: communication parity enabling
0 = parity not enabled
1 = parity enabled
bits 2-7: undefined
00 = IT
01 = EN
02 = FR
03 = DE
U8
U8
U16