Performance
Suitalbe fluids:
Max. percentage of glycol:
Maximum working temperature:
air separator side supply: 320°F (160°C)
pump side return:
Max. working pressure:
Safety relief valve working temperature range: -20 to 320°F (-30–160°C)
Safety relief valve setting:
Check valve min. opening pressure (Dp):
Shut-off and check valves working temperature range:
Flow meter working temperature range:
Flow rate adjustment range:
Flow rate indicator accuracy:
Pressure gauge scale:
Temperature gauge scale:
Connections:
Hose connection:
Fill/drain connections:
with hose connection 9/16" OD (15 mm)
water, glycol solution
50%
230°F (110°C)
145 psi (10 bar)
90 psi (6 bar)
1/4 psi (2 kPa)
-20 to 320°F (-30–160°C)
15 to 230°F (-10–110°C)
2 to 8 gpm
±10%
0 to 145 psi (0–10 bar)
32 to 320°F (0–160°C)
3/4" female straight thread
3/4" M
3
Pump model Solar 15-68
Body:
Electric supply:
Max. pressure:
Max. liquid temperature:
Min. liquid temperature:
Max. current:
Max. power consumption:
Protection class:
Flow range:
Head range:
Pump model UP-100 Drainback
Body:
Electric supply:
Max. pressure:
Max. liquid temperature:
Min. liquid temperature:
Max. current:
Max. power consumption:
Agency approval:
Flow range:
Head range:
NOTE: pump data per manufacturer technical specifications.
cast iron GG 15/20
115 V 60 Hz
150 psi (10 bar)
230°F (110°C)
36°F (2°C)
0.61 A
70 W
IP 42
0 to 10 gpm (0 to 2.3 m³/hr)
0 to 33 ft (0 to 10 m)
cast iron GG 15/20
115 V 60 Hz
150 psi (10 bar)
205°F (96°C)
36°F (2°C)
1.1 A
135 W
cULus
0 to 8.4 gpm (0 to 1.9 m³/hr)
0 to 36 ft (0 to 11.0 m)