Alderon Industries Versa'larm 4X Manual de operação, manutenção e instalação
Procurar online ou descarregar pdf Manual de operação, manutenção e instalação para Sistema de segurança Alderon Industries Versa'larm 4X. Alderon Industries Versa'larm 4X 3 páginas. Outdoor alarm system
Versa'larm 4X
Outdoor Alarm System
Operation, Maintenance and Installation Manual
Introduction
Before proceeding with the installation or operation of the Versa'larm™ 4X, read all
instructions thoroughly, as well as complying with all Federal, State and Local Codes,
Regulations and Practices. The Versa'larm 4X must be installed by qualified personnel
familiar with all applicable local electrical and mechanical codes. Refer to the National
Electrical Code (NFPA 70). Failure to properly install and test this product can result in
personal injury or equipment malfunction.
The Versa'larm 4X is a multipurpose alarm that can be used in a wide variety of applica-
tions such as: septic tanks, sumps, holding tanks, pump chambers and water tanks.
Safety Guidelines
1. DO NOT USE WITH FLAMMABLE OR EXPLOSIVE FLUIDS SUCH AS GASOLINE, FUEL OIL, KEROSENE,
ETC. DO NOT USE IN EXPLOSIVE ATMOSPHERES.
2. DICONNECT ALL POWER WHEN INSTALLING, WORKING ON THE UNIT OR REPLACING THE FUSE.
3. FAILURE TO TURN OFF ALL POWER WHEN SERVICING THE VERSA'LARM 4X COULD RESULT IN
SERIOUS INJURY OR DEATH.
Description of Operation
The Versa'larm 4X is powered by 120 VAC, "hard wired". When power is applied, the green "Power" indicator
light (located externally) will illuminate. When a float switch "closes" the buzzer and beacon will turn "on".
Pressing the "Silence" button deactivates the buzzer and the optional auxiliary contacts. When the alarm is
remedied, the system automatically resests itself. The system can be tested be pressing the "Test" switch, when
pressing the switch, the buzzer should annunciate and the beacon should illuminate. The auxiliary contacts are
activated when an alarm condition occurs. The single pole double throw contacts can switch a maximum of 5
amps at 120 VAC.
Electrical Information
Primary Power:
120 VAC, 50/60 Hz
Watts:
10 Watts
Fuse:
1 Amp Fast Acting Type AGC
Auxiliary Contacts:
Single Pole, Double Throw
5 Amps at 120 VAC
Buzzer:
85db at 10 Feet
Switch:
UL Listed, 120 VAC, 1 Amp Minimum
(signaling device)
Single Pole, Single Throw
Alarm Systems
Control Panels
PO Box 827 Hawley, MN 56549 (218) 483-3034 Fax (218) 483-3036 www.alderonind.com
TM
Float Switches
Leak Detection Systems
P/N: 10045 Rev. B
Page 1 of 2