eControls C365T11 Manual do instalador e do utilizador - Página 5
Procurar online ou descarregar pdf Manual do instalador e do utilizador para Termostato eControls C365T11. eControls C365T11 13 páginas.
Também para eControls C365T11: Manual do utilizador (4 páginas), Manual do instalador e do utilizador (13 páginas)
INSTALLER OPTIONS
Option
Description
01
Compressor Stages
02
Heating Stages.
03
Fan Operation.
04
Compressor Minimum Off Time (minutes).
05
Gas Minimum Off Time (minutes).
06
Minimum Run Time (minutes).
07
On-Off Temperature Differential
Differential Mode0 0.5 F On/Off span.
Differential Mode1 1.0 F On/Off span.
Differential Mode2 1.5 F On/Off span.
08
Smart Recovery.
09
Vacant Heating Setpoint.
10
Vacant Cooling Setpoint.
Calibrate Living Area Sensor
11
12
Calibrate Sleeping Area Sensor.
13
Airflow Update Time
14
Night Level LCD Backlight
15
Airflow Control On or Off
16
Enable USER Airflow Control
17
Maximum Airflow in Heating to the Sleeping Area.
18
Maximum Airflow in Cooling to the Sleeping Area.
19
Maximum Airflow in Heating to the Living Area.
20
Maximum Airflow in Cooling to the Living Area.
Maximum Temperature Difference Between
21
Sleeping and Living Area.
22
Factory Restore
ACCESSING INSTALLER OPTIONS
To access the Installer Options,
key for 7 seconds until the first Option appears on the screen.
Sleeping
Airflow %
Living
Day
Tu
AM
MENU
MODE
The hidden BACK key can be
used to return to previous options.
Press the touchscreen with your fingertip only, using a firm
!
touch. Do not use a sharp object such as a pen or pencil.
!
The NEXT key is used to display the next option.
The ENTER key is used to save options and return to normal
!
thermostat operation.
The hidden BACK key is used to return to previous options
!
and is located to the left of the NEXT key.
o
o
o
TOUCH
and
HOLD
the hidden Enter
Cool
Set To
Schedule
Living
COOL
SYSTEM
AUTO
FAN
TOUCH
and
HOLD
this key for 7 seconds
to access the Installer Options.
Display
Range
CPr
0 or 1
HtG
0 or 1
FAn
GA(Up) or EL(Down)
0 to 9
COt
HOt
0 to 9
r n t
0 to 9
O O o
0, 1 or 2
S r
0n(Up) or Off(Down)
V A C
+ Heat
44 to 75
V A C
+ Cool
74 to 95
C A L
+ Living
+/- 5
C A L
+ Sleeping
+/- 5
A F t
1 to 20 minutes
+ Night
BL
On(Up) or Off(Down)
AFC
On(Up) or Off(Down)
UAC
On(Up) or Off(Down)
100 to 160%
HAF+Heat
CAF+Cool
100 to 160%
HAF+Heat
100 to 160%
CAF+Cool
100 to 160%
diF
0 to 10
Fr
No(Next or Enter) or Yes(UP Key then Enter)
01 Setting the Compressor Stages
Use the
UP/DOWN
keys to set
0 or 1 stage.
Touch
NEXT
to display the
next option, or ENTER to save
the option
02 Setting the Heating Stages
Use the
UP/DOWN
keys to set
0 or 1 stage.
Touch
NEXT
or
ENTER.
03 Setting the Fan Operation in Heating
Touch the
UP
key to select
"EL" for electric operation
where the thermostat activates
the indoor fan (G terminal)
during heating calls or
DOWN
key to select GA for gas
operation where the equipment
plenum sensor activates the
indoor fan in heating calls.
5
Touch
NEXT
or
ENTER.
Default
1
1
GA
2
0
2
1
Off
65
80
0
0
2
On
On
Off
150%
140%
150%
140%
2
Option
NEXT
ENTER
Factory Default: 1 Stage. Range: 0 or 1
Option
NEXT
ENTER
Factory Default: 1 Stage. Range: 0 or 1
Option
NEXT
ENTER
Factory Default: Gas. Range: GA or EL