eControls T200WLD Manual do utilizador e do instalador - Página 7
Procurar online ou descarregar pdf Manual do utilizador e do instalador para Termostato eControls T200WLD. eControls T200WLD 8 páginas. Direct damper control
05 LCD Backlight
Skip this option. The LCD
uses LEDs to light the display.
Battery operated thermostats
light the LCD only when a key
is pressed to maintain battery
life. This option is set to 00
and cannot be changed.
Press the
NEXT
key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
06 Set High Setpoint Limit
The High Setpoint Limit is the
highest setpoint temperature
the user can set.
Press the
UP/DOWN
keys to
set the High Setpoint Limit
from 60 to 90 degrees.
Press the
NEXT
key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
07 Set Low Setpoint Limit
The Low Setpoint Limit is the
lowest setpoint temperature
the user can set.
Press the
UP/DOWN
keys to
set the Low Setpoint Limit
from 55 to 80 degrees.
Press the
NEXT
key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
08 Set Damper Factor
The Damper position is
adjusted proportional to the
differential between setpoint
and room temperatures. The
Damper Factor is the percent
change in damper position or
airflow for one degree of
temperature differential.
Press the
UP/DOWN
keys to set the Damper Factor from 8%
to 16%.
Press the NEXT key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
SYSTEM
Option
CANCEL
NEXT
ENTER
SYSTEM
Option
CANCEL
NEXT
ENTER
SYSTEM
Option
CANCEL
NEXT
ENTER
SYSTEM
Option
CANCEL
NEXT
ENTER
7
09 Set Nighttime Airflow
The Nighttime Airflow is the
airflow level that is
automatically set when using
the scheduled nighttime
setback. The lower airflow
reduces energy consumption.
Press the
UP/DOWN
keys to set the Nighttime Airflow from 0%
to 100%.
Press the NEXT key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
10 Set Off Airflow Level
The Off Airflow is the airflow
level that is automatically set
when the System is set to Off.
The lower airflow reduces
energy consumption.
Press the UP/DOWN keys to
set the Off Airflow from 0% to 100%.
Press the NEXT key to go to the next option. Or, press the
ENTER key to save and exit installer options, or press the
CANCEL key to exit installer options without saving.
1) Damper Installation
The damper or dampers controlling airflow to the space should
be installed in the supply duct providing airflow to the space.
In commercial installations the damper can be installed into the
supply diffuser.
The dampers should be mechanically supported and sealed
after installation. Although the dampers can be installed in any
orientation, it is desirable to install them where the LED
indicators on the damper actuators can be seen to verify they
are opening and closing.
2) Damper Wiring
The dampers are factory set for Zone1 and Address 1.
The dampers are powered by
24VAC and require only 2.8VA
when operating and only 1VA
when holding.
A 40VA transformer can power
up to 10 dampers.
SYSTEM
Option
CANCEL
NEXT
ENTER
SYSTEM
Option
CANCEL
NEXT
ENTER
Model A80WLD
Wireless Airflow Control
24VAC
Modulating
24VAC, 2.8VA
24VAC
eControls
Z#
Laguna Hills, CA
A#
Made in USA
To 24VAC
Transformer